NORD Drivesystems BU0200 User Manual
Page 205
SK 200E Manual for frequency inverters
204
Subject to technical alterations
BU 0200 GB-4411
Value Function
Description
Signal
75
Dig.out. 2 man/auto set
"Set digital output 2 manually / au-
tomatically"
As for function 67, however for digital output 2 (only SK 2x0E)
High
76
Dig.out. 2 man. set
"Set digital output 2 manually"
As for function 68, however for digital output 2 (only SK 2x0E)
High
1
If neither of the digital inputs is programmed for left or right enable, then the actuation of a fixed frequency or jog frequency will
enable the frequency inverter. The rotation field direction depends on the sign of the setpoint.
2
Also effective for Bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface)
3
With SK 2x5 devices the frequency inverter control unit must be supplied with power for a further 5 minutes after the last change
to the motor potentiometer in order to permanently save the data.
4
Function cannot be selected via BUS IO In Bits
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P426
Quick stop time
(Quick stop time)
S
P
0 ... 320.00 s
{ 0.10 }
Setting of the stop time for the quick stop function that can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
Quick stop time is the time for the linear frequency decrease from the set maximum frequency
(P105) to 0Hz. If an actual setpoint <100% is being used, the quick stop time is reduced
correspondingly.
P427
Quick stop on error
(Emergency stop on error)
S
0 ... 2
{ 0 }
Activation of automatic emergency stop following error
0 = Disabled: Automatic quick stop following error is deactivated
1 = reserved
2 = Enabled: Automatic quick stop following fault
P428
Automatic starting
(Automatic starting)
S
0 ... 1
{ 0 }
In the standard setting (P428 = 0 Off) the inverter requires a flank for enable (signal change
from "Low High") at the applicable digital input.
In the setting On 1 the FI reacts to a High level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. This means that
P428 = 1 On can be set. If the enable signal is permanently switched on, or equipped with a
cable jumper, the FI starts up immediately.
NOTE:
The "Automatic start" function can only be used if a digital input of the frequency
inverter (DIN
1 … DIN 4) is parameterised to the function "Enable right" or "Enable
left" and this input is permanently set to "High". The digital inputs of the
Technology Unit modules (e.g.: SK CU4 - IOE) do not support this "automatic start"
function.
NOTE:
The "Automatic start" can only be activated if the frequency inverter has been
parameterised to local control ((P509) setting { 0 } or { 1} ).