7 Status messages
BU 0200 GB-4411
Subject to technical alterations
263
Display in the
SimpleBox
Error
Text in the Parameter Box
Cause
Remedy
Group
Details in
P700[-01] /
P701
E010
10.0
Bus timeout
(Telegram timeout /
Bus off 24V int. CANbus)
Data transfer is faulty. Check P513.
Check external bus connection.
Check bus protocol program process.
Check Bus master.
Check 24V supply of internal CAN/CANopen Bus.
Nodeguarding error (internal CANopen)
Bus Off error (internal CANbus)
10.2
Bus timeout Option
(External bus module telegram
time-out)
Telegram transfer is faulty.
Check external connection.
Check Bus Protocol program process.
Check Bus master.
10.4
Initiation error, Option
(External bus module
initialisation failure)
Check Bus module current supply.
DIP switch setting of a connected I/O extension module is
incorrect
10.1
System error, Option
(Bus module)
Further details can be found in the relevant additional BUS
operating instructions.
I/O extension:
Incorrect measurement of the input voltage or undefined
provision of the output voltage due to error in reference
voltage generation.
Short circuit at analog output
10.3
10.5
10.6
10.7
10.9
Missing Option /P120
Module entered in P120 is not available.
E011
11.0
Control terminals
(Customer Unit)
(analog/digital converter error)
Internal Customer Unit (internal data bus) faulty or disturbed
by radio emissions (EMC).
Check control terminals connection for short-circuit.
Minimise EMC interference through separate laying of
control and power cables.
Device and shielding must be well earthed.