2 configuration – NORD Drivesystems BU0200 User Manual
Page 85
SK 200E Manual for frequency inverters
84
Subject to technical alterations
BU 0200 GB-4411
3.4.3.2
Configuration
The configuration of the system bus settings and the functions of the analog inputs and outputs is made via
a 12-part DIP switch element. Both analog inputs are differential inputs. The input voltage is simultaneously
measured in a unipolar and bipolar manner. The evaluation is unipolar or bipolar, according to the DIP
switch setting, with or without offset, as a current or voltage input.
If the module is configured for fail-safe signals in case of cable breaks (
2…10V / 4 .. 20mA), with signal lev-
els < 1V / < 2mA the frequency inverter switches to the state "Start disabled" (See also P700 [-03]). This
monitoring function is always active, even if the analog inputs are parameterised to "No function".
Range
Function
DIP switch
meaning
DIP switch
combinations
Signal
allocation
(DIP No.)
BIT2
BIT1
BIT0
C
o
n
figu
ra
tion
o
f
a
n
a
log
I
Os
Mode
Second - IOE
2nd IOE Mode
(12)
0
1
first
SK-
…-IOE on FI
second SK-
…-IOE on FI
Analog output
AOUT
Aout Mode Bit 1
(11)
0
0
1
0
0
1
0
1
0 … 10V
2 … 10V
0 … 20mA
4 … 20mA
Aout Mode Bit 0
(10)
Analog input AIN2
Ain2 Mode Bit 2
(09)
0
0
0
1
1
0
0
1
0
0
0
1
0
0
1
0 … 10V
2 … 10V
-
10 … 10V
0 … 20mA
4 … 20mA
Ain2 Mode Bit 1
(08)
Ain2 Mode Bit 0
(07)
Analog input AIN1
Ain1 Mode Bit 2
(06)
0
0
0
1
1
0
0
1
0
0
0
1
0
0
1
0 … 10V
2
… 10V
-
10 … 10V
0 … 20mA
4 … 20mA
Ain1 Mode Bit 1
(05)
Ain1 Mode Bit 0
(04)
B
u
s
-
C
o
n
figu
ra
tion
Addressing
System bus
S-Bus Addr. Bit 1
(03)
0
0
1
1
0
1
0
1
Address 20 (for FI0 Addr. 32)*
Address 21 (for FI1 Addr. 34)*
Address 22 (for FI2 Addr. 36)*
Address 23 (for FI3 Addr. 38)*
S-Bus Addr. Bit 0
(02)
System bus
termination resistor
S-Bus term.
(01)
0
1
not set
set
*for DIP12 = ON: Address 10 … 13 instead of 20 … 23
NOTE
Up to software version V1.0 R1 of the I/O extension the setpoint value of the analog output
could be inverted via DIP switch 12:
DIP12 setting "OFF":
100% setpoint = 10V
0% setpoint = 0V
DIP12 setting "ON":
100% setpoint = 0V
0% setpoint = 10V
With newer versions, this setting is made in parameter (P163) "Inversion AOut".
NOTE
The setting of the DIP switches is only read out during the initialisation phase. Changes
made while running are therefore not taken into account.
The side of the DIP switch element corresponding to "ON" should be checked (see label on
the DIP switch element) as for process reasons, this may vary during the manufacture of
the module.