2 Assembly and installation

BU 0200 GB-4411

Subject to technical alterations

45

2.8 Electrical connection of SK 2xxE control unit

The control terminals are located on the inside of the frequency inverter connection unit. The assignment of
the terminals varies according to the version (SK 200E, 205E, 210E, …, 235E).

Connection terminals:

Screw terminals, 3.5 mm slot-head screwdriver

Connection cross-section: 0.2 ... 2.5mm

2

, AWG 24-14, rigid or flexible, without cable sleeves

(Size 4, terminal 79/80: also: … 4.0mm² rigid, AWG 24-12)

Tightening torque:

0.5 ... 0.6Nm

Control cable:

Lay and shield separately from the mains/motor cables

Control voltages,

External:

18…30V, min. 200mA, the current load increases according to the level of
equipment.
Used to supply the FI control unit and connected options.

NOTE

GND is a common reference potential for analogue and digital inputs.