7 electrical connection of the power unit – NORD Drivesystems BU0200 User Manual

Page 41

background image

SK 200E Manual for frequency inverters

40

Subject to technical alterations

BU 0200 GB-4411

L1 / L

L2 / N

L3 / -

PE

PE L3 L2 L1

M

3~

PE U V W +B -B

Internal or

external braking

resistor

2.7 Electrical connection of the power unit

All connection terminals are located in the connection
unit of the frequency inverter.

One terminal block is provided for the power
connections and one for the control connections.

The earthing connections (device earthing) are
located on the base in the cast housing of the
connection unit. For size 4 a contact is available on
the power terminal block.

Before and while the device is connected, the
following must be observed:

1. Ensure that the mains supply provides the correct

voltage and is suitable for the current required
(see Section 8 Technical Data).

2. Ensure that suitable circuit breakers with the

specified nominal current range are installed
between the voltage source and the inverter.

3. Connect the mains voltage directly to the

terminals
L

1

-L

2

/N-L

3

und PE (according to the device).

4. To connect the motor, three flexible wires U-V-W

should be used when mounting the motor.

5. For wall-mounting a 4-conductor shielded motor

cable (recommended) to the terminals U-V-W and
earth should be used. In this case the cable
shielding should be connected to a large area of
the metallic screw connector.

NOTE:

If certain wiring sleeves are used, the maximum connection cross-section can be reduced.

Screwdriver: Use a 5.5mm slot-head screwdriver to connect the power unit.

NOTE:

If synchronous machines or several motors are connected in parallel to a device, the
frequency inverter must be switched over to linear voltage/frequency characteristic curves,
 P211 = 0 and P212 = 0.

NOTE:

Only use copper cables with min. 80°C or equivalent for connection. Higher temperature
classes are permissible.

NOTE:

The use of shielded cables is essential in order to maintain the specified radio interference
suppression level. (See also Section 9.4 EMC limit value classes)

ATTENTION:

This device produces high frequency interference, which may make additional suppression

measures necessary in domestic environments. (Details in Section. 9.3 / 9.4 (EMC))