5 control clamps – NORD Drivesystems BU0200 User Manual
Page 193
SK 200E Manual for frequency inverters
192
Subject to technical alterations
BU 0200 GB-4411
6.1.5
Control clamps
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P400
[-01]
...
[-09]
Fnct. setpoint inputs
(Function of setpoint inputs)
SK 2x0E
P
0 ... 33
{ [-01] = 1 }
{ [-02] = 0 }
{ [-03] = 0 }
{ [-04] = 0 }
{ [-05] = 1 }
{ [-06] = 0 }
a)
{ [-06] = 1 }
b)
{ [-07] = 1 }
a)
{ [-07] = 15 }
b)
{ [-08] = 0 }
{ [-09] = 0 }
SK
2x0E S 1 … 3
a)
SK2x0E S 4
b)
[-01] = Analog input 1, Function of analog input 1 integrated into the FI
[-02] = Analog input 2, Function of analog input 2 integrated into the FI
[-03] = Ext. analog input 1, AIN1 of the first I/O extension (SK xU4-IOE)
[-04] = Ext. analog input 2, AIN2 of the first I/O extension (SK xU4-IOE)
[-05] = Setpoint module, in preparation
[-06] = Digital input 2, can be set to pulse signal
evaluation via P420 [-02] =26 or 27. The
pulses are then evaluated in the FI as an
analog signal according to the function
which is set here.
[-07] = Digital input 3, can be set to pulse signal
evaluation via P420 [-03] =26 or 27. The
pulses are then evaluated in the FI as an
analog signal according to the function
which is set here.
[-06] = Potentiometer 1, Function of
the potentiometer P1 integrated
into the FI (Section 5.2.2). DIP
switches 4/5 must be "Off"
(Section 5.2.2), in order that the
function can be influenced by
this parameter setting
[-07] = Potentiometer 2, as for
potentiometer 1.
[-08] = Ext. A.in 1 2nd IOE, "External analog input 1 2nd IOE", AIN1 of the second I/O
extension (SK xU4-IOE) (= Analog input 3)
[-09] = Ext. A.in 2 2nd IOE, "External analog input 2 2nd IOE", AIN2 of the second I/O
extension (SK xU4-IOE) (= Analog input 4)
... setting values below.
P400
[-01]
...
[-09]
Fnct. setpoint inputs
(Function of setpoint inputs)
SK 2x5E
P
0 ... 33
{ [-01] = 1 }
{ [-02] = 15 }
{ [-03] = 0 }
{ [-04] = 0 }
{ [-05] = 1 }
{ [-06] = 0 }
{ [-07] = 1 }
{ [-08] = 0 }
{ [-09] = 0 }
[-01] = Potentiometer 1, Function of the potentiometer P1 integrated into the FI (Section
5.2.2). DIP switches 4/5 must be "Off" (Section 5.2.2), in order that the function can be
influenced by this parameter setting
[-02] = Potentiometer 2, as for potentiometer 1
[-03] = Ext. analog input 1, AIN1 of the first I/O extension (SK xU4-IOE)
[-04] = Ext. analog input 2, AIN2 of the first I/O extension (SK xU4-IOE)
[-05] = Setpoint module, in preparation
[-06] = Digital input 2, can be set to pulse signal evaluation via parameter P420 [-02] =26 or
27. The pulses are then evaluated in the FI as an analog signal according to the
function which is set here.
[-07] = Digital input 3, can be set to pulse signal evaluation via parameter P420 [-03] =26 or
27. The pulses are then evaluated in the FI as an analog signal according to the
function which is set here.
[-08] = Ext. A.in 1 2nd IOE, "External analog input 1 2nd IOE", AIN1 of the second I/O
extension (SK xU4-IOE) (= Analog input 3)
[-09] = Ext. A.in 2 2nd IOE, "External analog input 2 2nd IOE", AIN2 of the second I/O
extension (SK xU4-IOE) (=Analog input 4)