NORD Drivesystems BU0200 User Manual
Page 79
SK 200E Manual for frequency inverters
78
Subject to technical alterations
BU 0200 GB-4411
Details of the control connections
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
44
24V
24V supply
24VDC ±10%
max. 420mA (total)
integrated
short-circuit monitoring,
limited overtemperature
and overload monitoring
Supply voltage (output) to supply
an SK 2x5E or other module with
24V.
Can also be used as an input (in
this case, do not connect L1 and
L2), if the module is only to be
used as a voltage or frequency
converter (for the connection of a
potentiometer).
-
40
GND/0V
GND
Reference potential
-
44
24V
24V supply
-
40
GND/0V
GND
Reference potential
-
11
10V REF
+10V
reference voltage
10V ± 0.2V
Max.
load 5mA
For connection of potentiometer
5 -
10kΩ.
A
500Ω burden resistor for the
evaluation of 0/4 - 20mA signals is
contained in the enclosed bag.
-
14
AIN1+
Analog input 1
positive
0 … 10V,
Resolution: 8Bit
Accuracy: 0,2V
-
12 AGND/0V
Analog Ground
Reference potential for
analog signals
-
B1
DOUT
FOUT
Frequency output
SPS compatible in
compliance with
EN61131-2
Low: 0V, High: 24V
Pulse frequency:
~ 1 - 32kHz
Impulses for evaluation via the
digital input function P420 [02]/[03]
= 26/27 and the analog meaning in
P400 [-06]/[-07].
P420
P400
40
GND/0V
GND
Reference potential
-
Potential separation
L1
Mains connection
1. Phase
Mains connection, 100 - 240V or
380 - 500V, depending on the
module
-
L2
Mains connection
2. Phase
-
PE
PE, Earth
As required, does not need to be
connected.
-
PE
PE, Earth
-