6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
215
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P515
[-01]
…
...
[-03]
CAN bus address
(CAN bus address)
S
0 ... 255
dec
{ all 32
dec
}
or { all 20
hex
}
Setting of the system bus address.
[-01] = Slave address,system bus reception address
[-02] = Broadcast slave address, system bus reception address (slave)
[-03] = Broadcast master address, transmission address for system bus (master)
NOTE: If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows
FI1 = 32, FI2 = 34, FI3 = 36, FI4 = 38.
The system bus addresses should be set via the DIP switches S1:1/2 (Section 5.2.2.2).
P516
Skip frequency 1
(Skip frequency 1)
S
P
0.0 ... 400.0 Hz
{ 0.0 }
The output frequency around the frequency value (P517) set here is masked.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0.0 = Off: Masking frequency inactive
P517
Skip freq. area 1
(Skip frequency area 1)
S
P
0.0 ... 50.0 Hz
{ 2.0 }
Masking range for the >Masking frequency 1< P516. This frequency value is added and
subtracted from the masking frequency.
Masking frequency range 1: P516 - P517 to P516 + P517
P518
Skip frequency 2
(Skip frequency 2)
S
P
0.0 ... 400.0 Hz
{ 0.0 }
The output frequency around the frequency value (P519) set here is masked.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0.0 = Off: Masking frequency inactive
P519
Skip freq. area 2
(Skip frequency area 2)
S
P
0.0 ... 50.0 Hz
{ 2.0 }
Masking range for the >Masking frequency 2< P518. This frequency value is added and
subtracted from the masking frequency.
Masking frequency range 2: P518 - P519 to P518 + P519