SK 200E Manual for frequency inverters

216

Subject to technical alterations

BU 0200 GB-4411

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P520

Flying start

(Flying start)

S

P

0 ... 4

{ 0 }

This function is required to connect the FI to motors which are already rotating, e.g. in fan
drives. Motor frequencies >100Hz are only picked up in speed controlled mode (Servo mode
P300 = ON).

0 = Switched off, no flying start.

1 = Both directions, the FI looks for a speed in both directions.

2 = Directio of setpoint, "In setpoint value direction", searches only in the direction of the

setpoint value which is present.

3 = Both dir after fault, "Both directions after failure", only after mains failure and fault

4 = Dir of set a

fault, "In setpoint direction after fault", only after mains failure and fault

NOTE:

For physical reasons, the flying start circuit only operates above 1/10 of the
nominal motor frequency (P201), however, not below 10Hz.

Example 1

Example 2

(P201)

50Hz

200Hz

f=1/10*(P201)

f=5Hz

f=20Hz

Comparison of f with f

min

with:

f

min

=10Hz


Result f

Fly

=

5Hz < 10Hz

The flying start circuit
functions above
f

Fly

=10Hz.

20Hz > 10Hz

The flying start circuit
functions above
f

Fly

=20Hz.

P521

Fly. start resol.

(Flying start resolution)

S

P

0.02... 2.50 Hz

{ 0.05 }

Using this parameter, the flying start search increment size can be adjusted. Values that are
too large affect accuracy and causes the FI to cut out with an overcurrent report. If the values
are too small, the search time is greatly extended.

P522

Fly. start offset

(Flying start offset)

S

P

-10.0 ... 10.0 Hz

{ 0.0 }

A frequency value which is added to the frequency value found, e.g. to remain in the motor
range and so avoid the generator range and therefore the chopper range.

P523

Factory setting

(Factory setting)

0 ... 3

{ 0 }

By selecting the appropriate value and confirming it with the OK key, the selected parameter
range is entered in the factory setting. Once the setting has been made, the value of the
parameter automatically returns to 0.

0 = No change:Does not change the parameterisation.

1 = Load

factory

setting: The complete parameterisation of the FI reverts to the factory

setting. All originally parameterised data is lost.

2 = Fact setng wout bus, "Factory setting without bus": All parameters of the frequency

inverter, but not the bus parameters, are reset to the factory setting.

3 = Factory

set wo motor, "Factory setting without motor data": All parameters of the

frequency inverter, but not the motor data, are reset to the factory setting.

Note:

If an external EEPROM ("memory module"“) is plugged in, then a value of ("Factory
setting …") only affect this. If no "memory module" is present, the set command
("Factory setting …") is applied to the internal EEPROM (as of firmware version V 1.3).