NORD Drivesystems BU0200 User Manual
Page 198
6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
197
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P402
[-01]
...
[-06]
Adjust: 0%
(Analog input adjustment: 0%)
S
-50.00 ... 50.00 V
{ all 0.00 }
[-01] =
Ext analog in 1, "External analog input 1", AIN1 of the first I/O extension
(SK xU4-IOE).
[-02] =
Ext analog in 2, "External analog input 2", AIN2 of the first I/O extension
(SK xU4-IOE).
[-03] =
Ext. A.in 1 2nd IOE, "External analog input 1 2nd IOE", AIN1 of the second I/O
extension (SK xU4-IOE) (= analog input 3).
[-04] =
Ext. A.in 2 2nd IOE, "External analog input 2 2nd IOE", AIN1 of the second I/O
extension (SK xU4-IOE) (= analog input 4).
[-05] =
Analog input 1, Analog input 1 (only SK 200E, SK 210E)
[-06] =
Analog input 2, Analog input 2 (only SK 2x0E)
... only with
SK CU4-IOE or
SK TU4-IOE
This parameter sets the voltage which should correspond with the minimum value of the
selected function for the analog input 1 or 2. In the factory setting (setpoint) this value is
equivalent to the setpoint set via P104 >Minimum frequency<.
Note
SK 2x0E
For the adjustment of the integrated analog inputs of the SK2x0E to the type of analog signals,
the following values must be set:
0 - 10V
→ 0.00 V
2 - 10V
→ 2.00 V
0 - 20mA
→ 0.00 V (Set internal resistance via DIP switch (Section: 5.2.2.2)!)
4 - 20mA
→ 1.00 V (Set internal resistance via DIP switch (Section: 5.2.2.2)!)
SK xU4-IOE
Standardisation to typical signals, such as 0(2)-10V or 0(4)-20mA is carried out via the
DIP switch on the I/O extension module. In this case, additional adjustment of
parameters (P402) and (P403) must not be carried out.
P403
[- 01]
...
[- 06]
Adjust: 100%
(Analog input adjustment: 100%)
S
-50.00 ... 50.00 V
{ all 10.00 }
[-01] =
Ext analog in 1, "External analog input 1", AIN1 of the first I/O extension
(SK xU4-IOE).
[-02] =
Ext analog in 2, "External analog input 2", AIN2 of the first I/O extension
(SK xU4-IOE).
[-03] =
Ext. A.in 1 2nd IOE, "External analog input 1 2nd IOE", AIN1 of the second I/O
extension (SK xU4-IOE) (= analog input 3).
[-04] =
Ext. A.in 2 2nd IOE, "External analog input 2 2nd IOE", AIN1 of the second I/O
extension (SK xU4-IOE) (= analog input 4).
[-05] =
Analog input 1, Analog input 1 (only SK 200E, SK 210E)
[-06] =
Analog input 2, Analog input 2 (only SK 2x0E)
... only with
SK CU4-IOE or
SK TU4-IOE
This parameter sets the voltage which should correspond with the maximum value of the
selected function for the analog input 1 or 2. In the factory setting (setpoint) this value is
corresponds with the setpoint set via P105 >Maximum frequency<.
Note
SK 2x0E
For the adjustment of the integrated analog inputs of the SK2x0E to the type of analog signals,
the following values must be set:
0 - 10V
→ 10.00 V
2 - 10V
→ 10.00 V
0 - 20mA
→ 5.00 V (Set internal resistance via DIP switch (Section: 5.2.2.2)!)
4 - 20mA
→ 5.00 V (Set internal resistance via DIP switch (Section: 5.2.2.2)!)
SK xU4-IOE