NORD Drivesystems BU0200 User Manual
Page 207
SK 200E Manual for frequency inverters
206
Subject to technical alterations
BU 0200 GB-4411
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
16 = Reference value Ain1,
SK 2x0E:
Setpoint AIN1 of the FI is compared with the value in
(P435[-01 or -02]).
SK 2x5E: Setpoint AIN1 of the 1st IO extension is compared with the
value in (P435[-01]).
17 = Reference value Ain2,
SK 2x0E:
Setpoint AIN2 of the FI is compared with the value in
(P435[-01 or -02]).
SK 2x5E: Setpoint AIN2 of the 1st IO extension is compared with the
value in (P435[-01]).
18 = Inverter ready: The FI is in standby state. After being enabled it gives
an output signal.
High
19 = ... 29 reserved
For Posicon functions see BU 0210
30 = Status Digital-In 1*
High
Details for the
use of the bus
systems can be
found in the
relevant
supplementary
bus manual.
31 = Status Digital-In 2*
High
32 = Status Digital-In 3*
High
33 = Status Digital-In 4*
High
39 = STO inactive *
High
*) (P546[-
01]…[-03]) = 20
P435
[-01]
[-02]
Dig. out. scaling
(Scaling of digital outputs)
-400 ... 400 %
{ 100 }
[-01] =
Digital output 1, Digital output 1 of the frequency inverter
[-02] =
Digital output 2, Digital output 2 of the frequency inverter (only SK 2x0E)
Adjustment of the limit values of the output function. For a negative value, the output function
will be output negative.
Reference to the following values:
Current limit (3) = x [%]
P203 >Rated motor current<
Torque current limit (4) = x [%]
P203
P206 (calculated rated motor torque)
Frequency limit (5) = x [%]
P201 >Rated motor frequency<
P436
[-01]
[-02]
Dig. out. hysteresis
(Hysteresis of digital outputs)
S
0 ... 100 %
{ 10 }
[-01] =
Digital output 1, Digital output 1 of the frequency inverter
[-02] =
Digital output 2, Digital output 2 of the frequency inverter (only SK 2x0E)
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
P460
Watchdog time
(Time watchdog)
S
0.0 / 0.1 ... 250.0 s
{ 10.0 }
0.1 ... 250.0 = The time interval between the expected watchdog signals (programmable
function of digital inputs P420
– P425). If this time interval elapses without a
pulse being registered, switch off and error message E012 are actuated.
0.0 = Customer error: As soon as a high-low flank or a low signal is detected at a digital
input (function 18) the FI switches off with error message E012.