NORD Drivesystems BU0200 User Manual
Page 277
SK 200E Manual for frequency inverters
276
Subject to technical alterations
BU 0200 GB-4411
Size 2
Size 3
Device type:
SK 2xxE…
-151-323-A
-221-323-A
-301-323-A
-401-323-A
Nominal motor power
(4-pole standard motor)
230V
1.5 kW
2.2 kW
3.0 kW
4.0 kW
240V
2 hp
3 hp
4 hp
5 hp
In
p
u
t
Mains voltage
3~ 230V
3 AC 200 ... 240V,
10%, 47 ... 63 Hz
Typical input current
at 230V
3~ rms
6.6 A
9.1 A
11.8 A
15.1 A
3~ FLA
6.6 A
9.1 A
11.7 A
14.9 A
Rec. mains fuse
1 AC
slow-acting [A]
16 A
20 A
20 A
25 A
Permissible
mains fuses (UL)
RK5 or faster
fuses, min. 230V
10 A
30 A
30 A
30 A
Bussmann
FRS-R-10
FRS-R-30
FRS-R-30
FRS-R-30
Circuit breaker*
min. 230V
10 A
25 A
25 A
25 A
O
u
tp
u
t
Output voltage
3~ 230V
3 AC 0 - Mains voltage
Nominal output
current at 230V
rms
7.0 A
9.5 A
12.5 A
16.0 A
Motor
Assembly**
7.0A
(45°C)
9.5A
(45°C)
12.5A
(45°C)
16.0A
(45°C)
Wall-mounted**
5.5 A
5.5 A
8.0 A
8.0A
Min. braking resistor
62
62
33
33
Recommended braking
resistor
Section 2.3
200
200
100
100
Ω
Motor-mounting (ventilated), or wall mounting with SK TIE4-WMK-L-1 (or -2) (ventilated)
Max. continuous power / max. continuous current:
S1-50°C
S1-40°C
1.10kW / 7.0A
1.10kW / 7.0A
1.10kW / 9.2A
2.20kW / 9.5A
3.0kW / 12.5A
3.0kW / 12.5A
3.0kW / 14.5A
4.0kW / 16.0A
Max. permissible ambient temp. with nominal output current
S1
S3
70%ED 10min
S6
70%ED 10min (100% / 20%Mn)
50°C
50°C
50°C
49°C
50°C
50°C
50°C
50°C
50°C
46°C
47°C
47°C
Wall mounting (unventilated)
Max. continuous power / max. continuous current:
S1-50°C
S1-40°C
S1-30°C
0.55kW / 3.8A
0.75kW / 4.8A
1.10kW / 5.7A
0.75kW / 4.7A
1.10kW / 5.8A
1.10kW / 6.7A
1.1kW / 6.8A
1.5kW / 8.7A
2.2kW / 10.4A
1.1kW / 6.8A
1.5kW / 8.7A
2.2kW / 10.4A
Max. permissible ambient temp. with nominal output current
S1
S3
70%ED 10min
S6
70%ED 10min (100% / 20%Mn)
15°C
25°C
20°C
6°C
20°C
10°C
18°C
30°C
25°C
-4°C
0°C
0°C
* Circuit Breaker (inverse time trip type) as per UL489
** FLA (S1-40 °C)