3 motor data / characteristic curve parameters – NORD Drivesystems BU0200 User Manual
Page 183
SK 200E Manual for frequency inverters
182
Subject to technical alterations
BU 0200 GB-4411
6.1.3
Motor data / characteristic curve parameters
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P200
Motor list
(Motor list)
P
0 ... 45
{ 0 }
The factory settings for the motor data can be edited with this parameter. The factory setting in
parameters P201...P209 is a 4-pole DS standard motor with the nominal FI power setting.
By selecting one of the possible digits and pressing the OK key, all motor parameters
(P201…P209) are adjusted to the selected standard power. The basis for the motor data is a
4-pole DS standard motor.
0 = No change "No change of data"
1 = No motor: In this setting, the FI operates without current control, slip compensation and
pre-magnetising time, and is therefore not recommended for motor applications.
Possible applications are induction furnaces or other applications with coils and
transformers. The following motor data is set here:
50.0Hz / 1500rpm / 15.0A / 400V / 0.00kW / cos
=0.90 / star / R
S
0.01
/ I
EMPTY
6.5A
2 = 0.25 kW 230V
3 = 0.33 HP 230V
4 = 0.25 kW 400V
5 = 0.33 HP 460V
6 = 0.37 kW 230V
7 = 0.50 HP 230V
8 = 0.37 kW 400V
9 = 0.50 HP 460V
10 = 0.55 kW 230V
11 = 0.75 HP 230V
12 = 0.55 kW 400V
13 = 0.75 HP 460V
14 = 0.75 kW 230V
15 = 1.0 HP 230V
16 = 0.75 kW 400V
17 = 1.0 HP 460V
18 = 1.1 kW 230V
19 = 1.5 HP 230V
20 = 1.1 kW 400V
21 = 1.5 HP 460V
22 = 1.5 kW 230V
23 = 2.0 HP 230V
24 = 1.5 kW 400V
25 = 2.0 HP 460V
26 = 2.2 kW 230V
27 = 3.0 HP 230V
28 = 2.2 kW 400V
29 = 3.0 HP 460V
30 = 3.0 kW 230V
31 = 3.0 kW 400V
32 = 4.0 kW 230V
33 = 5.0 HP 230V
34 = 4.0 kW 400V
35 = 5.0 HP 460V
36 = 5.5 kW 230V
37 = 7.5 HP 230V
38 = 5.5 kW 400V
39 = 7.5 HP 460V
40 = 7.5 kW 230V
41 = 10 HP 230V
42 = 7.5 kW 400V
43 = 10 HP 460V
44 = 11.0 kW 400V
45 = 15.0 HP 460V
46 = 15.0 kW 400V
47 = 20.0 HP 460V
48 = 18.5 kW 400V
49 = 25.0 HP 460V
50 = 22.0 kW 400V
51 = 30.0 HP 460V
52 = 30.0 kW 400V
53 = 40.0 HP 460V
NOTE:
As P200 returns to = 0 after the input confirmation, the control of the set motor can
be implemented via parameter P205.
If DIP switch S1:7 (50/60Hz operation, Section 5.2.2.2) is switched over, the
appropriate nominal motor data according to the FI power rating are reloaded from
the P200 list.
P201
Nominal frequency
(Nominal motor frequency)
S
P
10.0 ... 400.0 Hz
{
}
The motor nominal frequency determines the V/f break point at which the FI supplies the
nominal voltage (P204) at the output.
P202
Nominal speed
(Nominal motor speed)
S
P
150 ... 24000 rpm
{
***
}
The nominal motor speed is important for the correct calculation and control of the motor slip
and the speed display (P001 = 1).
*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.