3 table of possible warning messages, N 7.3), And 7.3 – NORD Drivesystems BU0200 User Manual
Page 268
7 Status messages
BU 0200 GB-4411
Subject to technical alterations
267
7.3 Table of possible warning messages
Display in the
SimpleBox
Warning
Text in the Parameter Box
Cause
Remedy
Group
Details in
P700 [-02]
C001
1.0
Inverter
overtemp
"Inverter overtemperature"
(inverter heat sink)
Warning from output stage module (static)
Reduce ambient temperature <50°C or <40°C (see also
Section 8 Technical data).
Check control cabinet ventilation
C002
2.0
Motor overtemp PTC
"Overtemperature of motor
PTC"
(from thermistor)
Warning from motor temperature sensor (triggering
threshold reached)
Reduce motor load
Increase motor speed
Use external motor fan
2.1
Motor
overtemp I²t
"Overtemperature of motor from
I²t"
(Only if I
2
t- motor (P535) is
programmed.)
Warning: Motor I
2
t monitoring (Attainment of 1.3x the rated
current for the period specified in (P535))
Reduce motor load
Increase motor speed
2.2
Ext. resistor temp
"Overtemperature of external
brake resistor"
Overtemperature via digital
input (
P420 […])={13}
Warning: Temperature monitor has triggered
Digital input is Low
C003
3.0
Overcurrent I²t lim
"Overcurrent I²t limit"
Warning: Rectifier I
2
t limit,
(e.g. output current > NFI current rating)
(Attainment of 1.3x the inverter current rating for a period of
60 s)
Continuous overload at inverter output
(Please also note P504)
3.1
Overcurrent, chopper
"Overcurrent, chopper I2t"
Warning: I
2
t limit for brake chopper has triggered
(Attainment of 1.3x the value for a period of 60s)
(Please also note P555, P556, P557)
Avoid overcurrent in braking resistance
3.5
Torque limit
"Torque current limit"
Warning: torque current limit reached (P112)
3.6
Current limit
Warning: current limit reached (P536)