4 electrical data 3~400v – NORD Drivesystems BU0200 User Manual
Page 279
SK 200E Manual for frequency inverters
278
Subject to technical alterations
BU 0200 GB-4411
8.3.4
Electrical data 3~400V
Size 1
Device type:
SK 2xxE… -550-340-A
-750-340-A
-111-340-A
-151-340-A
-221-340-A
Nominal motor power
(4-pole standard motor)
400V
0.55 kW
0.75 kW
1.1 kW
1.5 kW
2.2 kW
480V
¾ hp
1 hp
1½ hp
2 hp
3 hp
In
p
u
t
Mains voltage
3~ 400V
3 AC 380 ... 500V, -20% / +10%, 47 ... 63 Hz
Typical input current
at 400V
3~ rms
1.6 A
2.2 A
2.9 A
3.7 A
5.2 A
3~ FLA
1.4 A
2.0 A
2.7 A
3.4 A
4.7 A
Rec. mains fuse
1 AC
slow-acting [A]
10 A
10 A
10 A
10 A
10 A
Permissible
mains fuses (UL)
RK5 or faster
fuses,
min 230V/400V
5.0 A
5.0 A
10 A
10 A
10 A
Bussmann
FRS-R-5
FRS-R-5
FRS-R-10
FRS-R-10
FRS-R-10
Circuit breaker*
min. 230V/400V
5.0 A
5.0 A
10 A
10 A
10 A
O
u
tp
u
t
Output voltage
3~ 400V
3 AC 0 - Mains voltage
Nominal output
current at 400V
rms
1.7 A
2.3 A
3.1 A
4.0 A
5.5 A
Motor
Assembly**
1.7A
(45°C)
2.3A
(45°C)
3.1A
(45°C)
4.0A
(45°C)
5.5A
(45°C)
Wall-mounted**
1.7A
(45°C)
2.3A
(45°C)
3.1A
(45°C)
4.0A
4.0A
Min. braking resistor
200
200
200
200
200
Recommended braking
resistor
Section 2.3
400
400
400
400
400
Ω
Motor-mounting (ventilated), or wall mounting with SK TIE4-WMK-L-1 (ventilated)
Max. continuous power / max. continuous current:
S1-50°C 0.55kW / 1.7A 0.75kW / 2.3A
1.10kW / 3.1A 1.10kW / 4.0A 2.20kW / 5.5A
Max. permissible ambient temp. with nominal output current
S1
S3
70%ED 10min
S6
70%ED 10min (100% / 20%Mn)
50°C
50°C
50°C
50°C
50°C
50°C
50°C
50°C
50°C
50°C
50°C
50°C
50°C
50°C
50°C
Wall mounting (unventilated)
Max. continuous power / max. continuous current:
S1-50°C
S1-40°C
S1-30°C
0.55kW / 1.7A
0.55kW / 1.7A
0.55kW / 1.7A
0.75kW / 2.3A
0.75kW / 2.3A
0.75kW / 2.3A
0.75kW / 2.8A
1.10kW / 3.1A
1.10kW / 3.1A
0.75kW / 2.8A
1.10kW / 3.3A
1.10kW / 3.9A
0.75kW / 2.8A
1.10kW / 3.3A
1.10kW / 3.9A
Max. permissible ambient temp. with nominal output current
S1
S3
70%ED 10min
S6
70%ED 10min (100% / 20%Mn)
50°C
50°C
50°C
50°C
50°C
50°C
45°C
50°C
50°C
29°C
40°C
35°C
1°C
15°C
5°C
* Circuit Breaker (inverse time trip type) as per UL489
** FLA (S1-40 °C)