8.3.4

Electrical data 3~400V

Size 1

Device type:

SK 2xxE… -550-340-A

-750-340-A

-111-340-A

-151-340-A

-221-340-A

Nominal motor power

(4-pole standard motor)

400V

0.55 kW

0.75 kW

1.1 kW

1.5 kW

2.2 kW

480V

¾ hp

1 hp

1½ hp

2 hp

3 hp

In

p

u

t

Mains voltage

3~ 400V

3 AC 380 ... 500V, -20% / +10%, 47 ... 63 Hz

Typical input current
at 400V

3~ rms

1.6 A

2.2 A

2.9 A

3.7 A

5.2 A

3~ FLA

1.4 A

2.0 A

2.7 A

3.4 A

4.7 A

Rec. mains fuse

1 AC

slow-acting [A]

10 A

10 A

10 A

10 A

10 A

Permissible
mains fuses (UL)

RK5 or faster

fuses,

min 230V/400V

5.0 A

5.0 A

10 A

10 A

10 A

Bussmann

FRS-R-5

FRS-R-5

FRS-R-10

FRS-R-10

FRS-R-10

Circuit breaker*

min. 230V/400V

5.0 A

5.0 A

10 A

10 A

10 A

O

u

tp

u

t

Output voltage

3~ 400V

3 AC 0 - Mains voltage

Nominal output
current at 400V

rms

1.7 A

2.3 A

3.1 A

4.0 A

5.5 A

Motor

Assembly**

1.7A

(45°C)

2.3A

(45°C)

3.1A

(45°C)

4.0A

(45°C)

5.5A

(45°C)

Wall-mounted**

1.7A

(45°C)

2.3A

(45°C)

3.1A

(45°C)

4.0A

4.0A

Min. braking resistor

200

200

200

200

200

Recommended braking
resistor

Section 2.3

400

400

400

400

400

Motor-mounting (ventilated), or wall mounting with SK TIE4-WMK-L-1 (ventilated)

Max. continuous power / max. continuous current:

S1-50°C 0.55kW / 1.7A 0.75kW / 2.3A

1.10kW / 3.1A 1.10kW / 4.0A 2.20kW / 5.5A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

Wall mounting (unventilated)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

S1-30°C

0.55kW / 1.7A

0.55kW / 1.7A

0.55kW / 1.7A

0.75kW / 2.3A

0.75kW / 2.3A

0.75kW / 2.3A

0.75kW / 2.8A

1.10kW / 3.1A

1.10kW / 3.1A

0.75kW / 2.8A

1.10kW / 3.3A

1.10kW / 3.9A

0.75kW / 2.8A

1.10kW / 3.3A

1.10kW / 3.9A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

50°C

50°C

50°C

50°C

50°C

45°C

50°C

50°C

29°C

40°C

35°C

1°C

15°C

5°C

* Circuit Breaker (inverse time trip type) as per UL489

** FLA (S1-40 °C)