NORD Drivesystems BU0200 User Manual
Page 204
6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
203
Value Function
Description
Signal
45
3-W-Ctrl. Start-Right
“3-Wire-Control Start-Right”
(Closing button)
This control function provides an alternative to enable R/L (01/ 02),
in which a permanently applied level is required.
Here, only a control impulse is required to trigger the function. The
control of the FI can therefore be performed entirely with buttons.
0
1
Flank
46
3-W-Ctrl Start-Left
“3-Wire-Control Start-Left”
(Closing button)
0
1
Flank
49
3-Wire-Ctrl. Stop
“3-Wire-Control Stop”
(Opening button)
10
Flank
47
Motorpot. Freq.
+
"
Motor potentiometer frequency +"
In combination with enable R/L the output frequency can be
continuously varied. To save a current value in P113, both inputs
must be at a High voltage for 0.5s. This value then applies as the
next starting value for the same direction of rotation (Enable R/L)
otherwise start at f
MIN
.
High
48
Motorpot. Freq.
-
"
Motor potentiometer frequency -"
High
50
Bit 0 Fixed frequency array
Binary coded digital inputs to generate up to 15 fixed frequencies.
(P465: [-01] ... [-15])
High
51
Bit 1 Fixed frequency array
High
52
Bit 2 Fixed frequency array
High
53
Bit 3 Fixed frequency array
High
55
… 64 reserved for Posicon BU 0210
65
2
Man/auto release brake
"Release brake manually/
automatically"
The brake is automatically released by the frequency inverter
(automatic brake control) if this digital input has been set.
High
66
2
Man. release brake
"Release brake manually"
The brake is only released of the digital input is set.
High
67
Dig.out. man/auto set
"Set digital output manually /
automatically"
Set digital output 1 manually, or via the function set in (P434)
High
68
Dig.out. man. set
"Set digital output manually"
Set digital output 1 manually
High
69
Speed meas. with ini.
"Speed measurement with
initiator"
Simple speed measurement (impulse measurement) with initiator
Impulses
70
Evacuation run
"Activate evacuation run"
This also provides the possibility of operation with a very low link
circuit voltage (e.g. using batteries). With this function the charging
relay is activated and the undervoltage and phase error detection
are deactivated.
ATTENTION! There is no overload monitoring! (e.g. lifting gear)
High
71
Motorpot.F+ and Save
"Motor potentiometer function
Frequency + with automatic
saving"
With this motor potentiometer function, a setpoint value is set and
saved via the digital inputs. With control enabling R/L this is then
started up in the correspondingly enabled direction. On change of
direction the frequency is retained.
Simultaneous activation of the +/- function causes the frequency
setpoint value to be set to zero.
The frequency setpoint value can also be displayed or set in the
operating value display (P001=30, current setpoint MP-S) or in P718.
Any minimum frequency set (P104) is still effective. Other setpoint
values, e.g. analog or fixed frequencies can be added or subtracted.
The adjustment of the frequency setpoint value is performed with
the ramps from P102/103.
High
72
Motorpot.F- and Save
"Motor potentiometer function
Frequency - with automatic
saving"
High
73 ²
Inhibit right+ Quick
"Inhibit turn right+ Quick Stop"
As for setting 31, but coupled to the "Quick Stop" function.
Low
74 ²
Inhibit left+ Quick
"Inhibit turn left+ Quick Stop"
As for setting 32, but coupled to the "Quick Stop" function.
Low
...continued on the next page