2 Assembly and installation
BU 0200 GB-4411
Subject to technical alterations
51
2.8.3
Details of the SK 2x5E control connections
Control voltage 24V external! Terminal 44. If the frequency inverter is not equipped with an optional mains
unit it must be supplied with an external 24V voltage.
For devices where the AS interface is used (SK 225E and SK 235E), the control voltage supply must be
provided via the yellow AS interface cable. In this case however, the frequency inverter must not have an
additional supply via Terminal 44 in order to prevent damage to the mains unit or the AS interface bus.
Terminal/
Name
Function
{Factory setting}
Data
Description / wiring suggestion
Parameter
SK 205E, SK 215E, SK 225E, SK 235E
44
24V
24V supply
Input
24VDC ± 25%
200mA (FI without
accessories) ... 800mA
according to load on the
inputs and outputs or
equipment with options
24VDC, max 60mA
Output voltage with use of
the AS interface
Supply voltage connection for the
FI control unit and the output
DOUT1
With SK 225/235E and use of the
AS interface (yellow cable) the
inverter is supplied by the AS
interface.
-
40 GND / 0V
Reference potential
for digital signals
-
21
DIN1
Digital input 1
{ON right}
Digital input as per
EN 61131-2 Type 1
Low: 0-5V
(~ 9.5k
Ω)
High: 15-30V
(~ 2.5-3.5k
Ω)
Input capacitance:
Input 1 + 4 = 10 nF
Input 2 + 3 = 1.2 nF
Scan time: 1ms
Reaction time:
≥ 4ms
HTL encoder connection
only to DIN2 and DIN3
possible
Frequency limits:
max. 205 kHz
min. 250 Hz
44
40
21
22
23
24
18
… 30V
GND / 0V
Inputs 1 + 4 react slowly
Inputs 2 + 3 react quickly
P420 [01]
22
DIN2
Digital input 2
{ON left}
P420 [02]
23
DIN3
Digital input 3
{fixed frequency 1,
(P465[-01])}
P420 [03]
24
DIN4
(only SK205/225E)
Digital input 4
{fixed frequency 2,
(P465 [-02])}
P420 [04]
1
DOUT1
Output 1
{Fault}
Digital output
18-30V, each to VI 24V
max. 200mA
max. 100k
load
For evaluation in a control system.
With SK 225/235E and use of the
AS interface (yellow cable),
DOUT1 must not be under load.
P434 [01]
38
TF+
PTC resistor input
-
For monitoring motor temperature
with PTC
A shielded cable must be used for
separate mounting of the motor
and the FI (note cable length).
-
39
TF-
PTC resistor input