2 customer units for atex zone 22 3d – NORD Drivesystems BU0200 User Manual
Page 62
2 Assembly and installation
BU 0200 GB-4411
Subject to technical alterations
61
Name
Part Number
Approved for
ATEX Zone 22 3D
Not approved for
ATEX Zone 22 3D
SK TU4-POT-123-B(-C)
275281110 / (275281160)
x
SK TU4-POT-140-B(-C)
275281111 / (275281161)
x
SK TU4-PBR-M12(-C)
275281200 / (275281250)
x
SK TU4-CAO-M12(-C)
275281201 / (275281251)
x
SK TU4-DEV-M12(-C)
275281202 / (275281252)
x
SK TU4-IOE-M12(-C)
275281206 / (275281206)
x
*Only SK 2x5E
2.10.2.2 Customer Units for ATEX Zone 22 3D
Name
Part Number
Approved for
ATEX Zone 22 3D
Not approved for
ATEX Zone 22 3D
SK CU4-PBR
275271000
x
SK CU4-CAO
275271001
x
SK CU4-DEV
275271002
x
SK CU4-IOE
275271006
x
SK CU4-POT
275271207
x
SK CU4-24V-123-B*
275271108
x
SK CU4-24V-140-B*
275271109
x
SK ATX-POT
275142000
x
*Only SK 2x5E
The SK 2xxE for Category 3D can be equipped with an ATEX-compliant potentiometer, which can be used
to adjust a setpoint (e.g. speed) on the device. The potentiometer is used with an M20-M25 extension in one
of the M25 cable glands. The selected setpoint can be adjusted with a screwdriver. Due to the removable
screw closing cap, this component complies with
ATEX requirements. Permanent operation may only
be carried out with the cap closed.
Frequency setpoint setting
with a screwdriver
Resistance of the potentiometer 10 kOhm
Wire colours on the
potentiometer
Name
Terminal SK CU4-24V*
Terminal SK CU4-IOE
Terminal SK 2x0E
Red
+10V reference
[11]
[11]
[11]
Black
AGND / 0V
[12]
[12]
[12] / [40]
Green
Analog input
[14]
[14] / [16]
[14] / [16]
*Only SK 2x5E
NOTE:
For use of a potentiometer with frequency inverter SK 2x5E a CU4-24V-xxx-B or CU4-IOE
customer unit is required! With the SK 2x0E, this can be connected directly to an integrated
analog input.