9.2.2
Process controller parameter settings
(Example: Setpoint frequency: 50 Hz, control limits: +/- 25%)
P105 (Maximum frequency) [Hz]
:
%
%
.
.
100
415
P
Hz
q
Setpointfr
Hz
q
Setpointfr
Example:
%
100
%
25
50
50
Hz
Hz
62,5Hz
P400 [-01] (Funct. Analog input1)
:
"2“" (frequency addition)
P411 (Setpoint frequency) [Hz]
: Setpoint frequency with 10V at analog input 1
Example: 50 Hz
P412 (Process controller setpoint) : Central setting of compensating roller / factory setting 5V (adjust if
necessary)
P413 (P-controller) [%]
: factory setting 10% (adjust if necessary)
P414 (I-controller) [%/ms]
: recommended 100%/s
P415 (Limit +/-) [%]
: Control limit (see above)
Note:
Parameter P415 is used as a control limit after the PI controller.
Example: 25% of setpoint
P416 (Ramp time PI setpoint) [s]
: factory setting 2s (if necessary match to controller characteristics)
P420 [-01] (Funct. Digital input 1)
: "1"Enable right
P400 [-02] (Funct. Analog input 2) : "6"PI process controller actual value