5 commissioning, 1 factory settings, 5 commissioning 5.1 factory settings – NORD Drivesystems BU0200 User Manual
Page 149
SK 200E Manual for frequency inverters
148
Subject to technical alterations
BU 0200 GB-4411
5 Commissioning
5.1 Factory settings
All frequency inverters supplied by Getriebebau NORD are pre-programmed with the default setting for
standard applications with 4 pole standard motors (same voltage and power). For use with motors with
other powers or number of poles, the data from the name plate of the motor must be input into the
parameters P201...P207 under the menu item >Motor data<.
NOTE:
All motor data can be pre-set using the parameter P200. After successful use of this
function, this parameter is reset to 0 = no change! The data is loaded automatically into
parameters P201...P209
– and can be compared again with the data on the motor name
plate.
3~ Mot
IEC 56
IM B3
cos
0,74
cos
0,74
IP55
Rot. KL 16
Th.Cl.F
EN60034
60 Hz
460 V Y
5,2 A
2,5 kW
1765 /min
1440 /min
P206
P201
P204
P203 P202
P200
9,0 /
5,2 A
50 Hz
2,2 kW
P207
P200 Motor list:
0 = no change
8 = 0.37 kW 400V
1 = no motor
9 = 0.50 HP 460V
2 = 0.25 kW 230V
10 = 0.55 kW 230V
3 = 0.33 HP 230V
11 = 0.75 HP 230V
4 = 0.25 kW 400V
12 = 0.55 kW 400V
5 = 0.33 HP 460V
13 = 0.75 HP 460V
6 = 0.37 kW 230V
14 = 0.75 kW 230V
7 = 0.50 HP 230V ....
230 /
400 V
/
Y
RECOMMENDATION: For the correct operation of the drive unit, it is necessary to input the motor data
according to the name plate as precisely as possible. In particular, an automatic
stator resistance measurement using parameter P220 is recommended.
In order to automatically determine the stator resistance, P220 = 1 must be set and
confirmed by pressing "OK". The value calculated for the line resistance
(dependent upon P207) will be saved in P208.
ATTENTION
After a default setting "Enable Left" or "Enable Right", the digital inputs DIN2 and DIN3 are
additionally assigned for the evaluation of an HTL incremental encoder. The encoder evaluation
function cannot be switched off. This means that with the use of an incremental encoder, it is
essential to set parameters (P420[-02]) and (P420[-03]) to "no function".
This can also be implemented with the inverter DIP switch (S1) (Section 5.2.2).
NOTE
It must be noted that DIP switch settings on the frequency inverter have priority over the
parameter settings.
In addition, the settings of the integrated potentiometers P1 and P2 must be taken into account.