NORD Drivesystems BU0200 User Manual
Page 278
8 Technical data
BU 0200 GB-4411
Subject to technical alterations
277
Size 4
Device type:
SK 2x0E…
-551-323-A
-751-323-A
-112-323-A
Nominal motor power
(4-pole standard motor)
230V
5.5 kW
7.5 kW
11.0 kW
240V
7½ hp
10 hp
15 hp
In
p
u
t
Mains voltage
3~ 230V
3 AC 200 ... 240V,
10%, 47 ... 63 Hz
Typical input current
at 230V
3~ rms
23.5 A
29.5 A
40.5 A
3~ FLA
22.5 A
28.5 A
39.0 A
Rec. mains fuse
1 AC
slow-acting [A]
35 A
50 A
50 A
Permissible
mains fuses (UL)
RK5 or faster
fuses, min. 230V
30 A
40 A
60 A
Bussmann
FRS-R-30
FRS-R-40
FRS-R-60
Circuit breaker*
min. 230V
30 A
40 A
60 A
O
u
tp
u
t
Output voltage
3~ 230V
3 AC 0 - Mains voltage
Nominal output cur-
rent at 230V
rms
23.0 A
29.0 A
40.0 A
Motor Assem-
bly**
23.0 A
29.0 A
40.0 A
Wall-mounted**
23.0 A
29.0 A
40.0 A
Min. braking resistor
30
20
15
Recommended braking
resistor
Sec. 2.3
47
47
23
Motor Assembly
Max. continuous power / max. continuous current:
S1-50℃
S1-40°C
5.5 kW / 23 A
5.5 kW / 23 A
7.5 kW / 29 A
7.5 kW / 29 A
7.5 kW / 29 A
11.0 kW / 40A
Max. permissible ambient temp. with nominal output current
S1
S3
70%ED 10min
S6
70%ED 10min (100% / 20%Mn)
50°C
50°C
50°C
50°C
50°C
50°C
42°C
44°C
44°C
Wall-mounting
Max. continuous power / max. continuous current:
S1-50°C
S1-40°C
5.5 kW / 23 A
5.5 kW / 23 A
7.5 kW / 29 A
7.5 kW / 29 A
7.5 kW / 29 A
11.0 kW / 40A
Max. permissible ambient temp. with nominal output current
S1
S3
70%ED 10min
S6
70%ED 10min (100% / 20%Mn)
50°C
50°C
50°C
50°C
50°C
50°C
42°C
44°C
44°C
* Circuit Breaker (inverse time trip type) as per UL489
** FLA (S1-40 °C)