44

Part 2 Operation


(2) Timing chart

[1] Program start








[2] Program start by auto-start

* When I/O parameter No. 33 is set to “2”






[3] Software reset signal

* When I/O parameter No. 31 is set to “1”








[4] Servo ON signal

* When I/O parameter No. 32 is set to “1”








[5] When the recovery action following an emergency stop or enable operation is set to “continued

operation”
* When other parameter No. 10 is set to “2”

Set I/O parameter No. 35 to “1” (Operation-pause reset signal)
Set I/O parameter No. 44 to “1” (Drive-source cutoff reset input)









Program 1

Program 2

Ready output

Program
number input

External start
input

T1: Duration after the ready output turns ON until

input of external start signal is permitted
T1 = 10 msec min.


T2: Duration after the program number is input until

input of external start signal is permitted
T2 = 50 msec min.


T3: Input duration of external start signal

T3 = 100 msec min.

Ready output

Input by input
function 003

Auto program
start

T1: Duration after the ready output turns ON, until

input by the input function 003 is permitted
T1 = 10 msec min.


*

Auto program start:
Set the program you want to start automatically
in other parameter No. 1, “Auto-start program
number.”

Ready output

Input by input
function 001

Program
starting

T1: Duration after the ready output turns ON, until

input by the input function 001 is permitted
T1 = 10 msec min.


T2: Duration until the software reset signal

becomes functional
T2 = 1 sec min.


T3: Duration after the software reset signal is reset,

until the ready signal is output

Ready output

Input by input
function 002


Servo ON

T1: Duration after the ready output turns ON, until

input by the input function 002 is permitted
T1 = 10 msec min.


T2: Interval after the servo turns off, until the servo

turns on again
T2 = 1.5 sec min.

Program
starting

Emergency
stop

Drive-source
cutoff reset

Pause reset

T1: Duration after the emergency stop input is reset,

until the drive-source cutoff reset signal can be
input
T1 = 2 sec min.


T2: Duration over which the drive-source cutoff reset

signal is input
T2 = 10 msec min.


T3: Duration over which the pause reset signal is input

T3 = 10 msec min.