I/o parameters – IAI America XSEL-KX User Manual
Page 308
![background image](/manuals/350295/308/background.png)
292
Appendix
1. I/O Parameters
No.
Parameter name
Default value
(Reference)
Input
range
Unit
Remarks
1
I/O port assignment type
1
0 ~ 20
0: Fixed assignment
1: Automatic assignment (Priority: Slot 1
(standard I/O) ~ * Ports are assigned only
for the installed adjoining slots, starting from
slot 1 = For safety reasons)
2
Input port start number with fixed
standard I/O assignments (I/O1)
000
-1 ~ 599
0 + (Multiple of 8) (Invalid if a negative value is
set)
3
Output port start number with fixed
standard I/O assignments (I/O1)
300
-1 ~ 599
300 + (Multiple of 8) (Invalid if a negative value
is set)
4
Input port start number with fixed
expanded I/O1 assignments (I/O2)
-1
-1 ~ 599
0 + (Multiple of 8) (Invalid if a negative value is
set) (Slot next to the standard I/O slot)
5
Output port start number with fixed
expanded I/O1 assignments (I/O2)
-1
-1 ~ 599
300 + (Multiple of 8) (Invalid if a negative value
is set)
6
Input port start number with fixed
expanded I/O2 assignments (I/O3)
-1
-1 ~ 599
0 + (Multiple of 8) (Invalid if a negative value is
set)
7
Output port start number with fixed
expanded I/O2 assignments (I/O3)
-1
-1 ~ 599
300 + (Multiple of 8) (Invalid if a negative value
is set)
8
Input port start number with fixed
expanded I/O3 assignments (I/O4)
-1
-1 ~ 599
0 + (Multiple of 8) (Invalid if a negative value is
set)
9
Output port start number with fixed
expanded I/O3 assignments (I/O4)
-1
-1 ~ 599
300 + (Multiple of 8) (Invalid if a negative value
is set)
10 Standard I/O error monitor (I/O1)
1
0 ~ 5
0: Do not monitor, 1: Monitor * Some
exceptions apply.
11 Expanded I/O1 error monitor (I/O2)
1
0 ~ 5
0: Do not monitor, 1: Monitor (Slot next to the
standard I/O slot) * Some exceptions apply.
12 Expanded I/O2 error monitor (I/O3)
1
0 ~ 5
0: Do not monitor, 1: Monitor * Some
exceptions apply.
13 Expanded I/O3 error monitor (I/O4)
1
0 ~ 5
0: Do not monitor, 1: Monitor * Some
exceptions apply.
14 Number of ports using network-I/F-
card remote input
0
0 ~ 256
Multiple of 8
15 Number of ports using network-I/F-
card remote output
0
0 ~ 256
Multiple of 8
16 (For future extension = Change
prohibited)
0
0 ~ 256
Multiple of 8
17 (For future extension = Change
prohibited)
0
0 ~ 256
Multiple of 8
18 ~
19
(For extension)
0
20 Input filtering periods
2
1 ~ 9
msec Input signal is recognized when the status is
held for twice the period set by this parameter.
21 Register input filtering periods
2
1 ~ 9
msec Input signal is recognized when the status is
held for twice the period set by this parameter.
22 Remote-I/O-card fieldbus ready
timeout value
2000
0 ~
99999
msec Timeout check is not performed if “0” is set.