(In the panel window, the three digits after “E” indicate an error number.)

Error No.

Error name

Description, action, etc.

813

Maintenance information 3

Maintenance information (for analysis)

814

Maintenance information 4

Maintenance information (for analysis)

815

Maintenance information 5

Maintenance information (for analysis)

900

Blank step shortage error

There are not enough blank steps to save step data. Provide enough blank
steps needed to save step data.

901

Step number error

The step number is invalid.

902

Symbol-definition table number error

The symbol-definition table number is invalid.

903

Point number error

The point number is invalid.

904

Variable number error

The variable number is invalid.

905

Flag number error

The flag number is invalid.

906

I/O port/flag number error

The I/O port/flag number is invalid.

910

Command error (IAI protocol HT reception)

The command ID is not supported or invalid. (For future extension)

911

Message conversion error (IAI protocol HT reception)

The transmitted message does not match the message format or contains
invalid data. (For future extension)

930

Coordinate system number error

The coordinate system number is invalid.

931

Coordinate system type error

The coordinate system type is invalid.

932

Coordinate system definition data count-specification error

The specified number of coordinate system definition data is invalid.

933

Axis number error

The axis number is invalid.

934

Operation type error for SCARA ABS-reset special movement

The operation type for SCARA ABS-reset special movement is invalid.

935

Positioning operation type error

The positioning operation type is invalid.

936

Simple interference check zone number error

The simple interference check zone number is invalid.

938

Simple interference check zone data count-specification error

The specified number of simple interference check zone data is invalid.

939

Detection of entry into simple interference check zone (Message
level specification)

Entry into the simple interference check zone was detected. (Message level
specification)

93A

R-axis CP jog prohibition error when out of operation range (When
tool XY offset is valid)

Move into the operation range by jogging each axis.

A01

System-memory backup battery voltage-low warning

The voltage of the system-memory backup battery is low. Replace the battery.
(Above the minimum data-backup voltage)

A02

Abnormal system-memory backup battery voltage

The voltage of the system-memory backup battery is low. Replace the battery.
(Below the minimum data-backup voltage)

A03

Absolute-data backup battery voltage-low warning (Driver detection) The voltage of the absolute-data backup battery is low. Check the battery

connection or replace the battery.

A04

System mode error at core update

An update command was received when the system was not in the core update
mode. Before updating the core, confirm that a chip resistance for setting core
update mode is provided on the board. (For maintenance)