Setting of motor electronic thermal protection level 1 VJT

If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller
than the rated current of the inverter, adjust the electronic thermal protection level 1 VJT so that it fits the motor's
rated current.
* If the indications are in percentages[%], then 100% equals the inverter's rated output current [A].

VJT

×0.6

VJT

×1.0

H

=Hz

Output frequency [Hz]

Output current reduction factor [%]/[A]

0

Setting the motor overload starting level

2) Motor 150%-overload time limit H

The motor 150%-overload time limit parameter H is used to set the time elapsed before the motor trips under
a load of 150% (overload trip QN) within a range of 10 to 2400 sec.

[Example setting]

Monitored output

current [%]

Motor overload time [s] (Outline data)

H

=

H

=

VJT

= VJT=

H

0.01Hz

H

0.01Hz

68

34

7200

3600

70

35

3600

1800

80

40

1000

500

90

45

600

300

100

50

420

210

112

56

12000

310

6000

155

120

60

2400

270

1200

135

130

65

1200

230

600

115

140

70

800

190

400

95

150

75

600

170

300

85

200

100

270

110

135

55

Monitored output current [%]

time [s]

Motor 150%-
overload time limit

H

Motor overload

0

VJT

×0.6

VJT

×1

.1

VJT

×1.5

Operation
frequency
no less than

H

Operation frequency

0.01Hz *1

*1 Except for the cases of

H

=

,

[Hz]

Motor overload protection characteristics

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Motor 150%-overload time limit

~ sec.