Toshiba Tosvert VF-AS1 User Manual
Page 89

E6581301
E-23
5
■
Setting of motor electronic thermal protection level 1 VJT
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller
than the rated current of the inverter, adjust the electronic thermal protection level 1 VJT so that it fits the motor's
rated current.
* If the indications are in percentages[%], then 100% equals the inverter's rated output current [A].
VJT
×0.6
VJT
×1.0
H
=Hz
Output frequency [Hz]
Output current reduction factor [%]/[A]
0
Setting the motor overload starting level
2) Motor 150%-overload time limit H
The motor 150%-overload time limit parameter H is used to set the time elapsed before the motor trips under
a load of 150% (overload trip QN) within a range of 10 to 2400 sec.
[Example setting]
Monitored output
current [%]
Motor overload time [s] (Outline data)
H
=
H
=
VJT
= VJT=
H
0.01Hz
H
0.01Hz
68
34
–
7200
–
3600
70
35
–
3600
–
1800
80
40
–
1000
–
500
90
45
–
600
–
300
100
50
–
420
–
210
112
56
12000
310
6000
155
120
60
2400
270
1200
135
130
65
1200
230
600
115
140
70
800
190
400
95
150
75
600
170
300
85
200
100
270
110
135
55
Monitored output current [%]
time [s]
Motor 150%-
overload time limit
H
Motor overload
0
VJT
×0.6
VJT
×1
.1
VJT
×1.5
Operation
frequency
no less than
H
Operation frequency
0.01Hz *1
*1 Except for the cases of
H
=
,
[Hz]
Motor overload protection characteristics
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Motor 150%-overload time limit
~ sec.