Toshiba Tosvert VF-AS1 User Manual

Page 241

background image

K-3

E6581301

11

1. Basic parameter [3/4]

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control

V/f

Reference

VJT

0600

Motor overload protection

level 1

10~100%

1/1

100

Enabled

●/●

●/●

5. 14

Setting Motor type

Overload

protection

OL stall

0

○ (protect)

× (not stall)

1

○ (protect)

○ (stall)

2

× (not protect)

× (not stall)

3

Standard

Motor

× (not protect)

○ (stall)

4

○ (protect)

× (not stall)

5

○ (protect)

○ (stall)

6

× (not protect)

× (not stall)

QNO

0017

Motor overload protection

characteristic selection

7

VF Motor

× (not protect)

○ (stall)

1/1

0

Enabled

●/●

5. 14

5. 14

FURW

0701

Current/voltage unit

selection

0:%, 1:A (ampere)/V (volt)

1/1

0

Enabled

●/●

●/●

5. 15

HOUN

0005

FM terminal meter

selection

0~64 *1

1/1

0

Enabled

●/●

●/●

5. 16

HO

0006

FM terminal meter

adjustment

-

1/1

-

Enabled

●/●

●/●

5. 16

COUN

0670

AM terminal meter

selection

0~64 *1

1/1

2

Enabled

●/●

●/●

5. 16

CO

0671

AM terminal meter

adjustment

-

1/1

-

Enabled

●/●

●/●

5. 16

EH

0300

PWM carrier frequency

1.0~16.0kHz (1.0~8.0kHz) *2

0.1/0.1

*3

Enabled

●/●

●/●

5. 17

WXU

0301

Auto-restart control

selection

0:Deselect

1:At auto-restart

2:ST ON/OFF switching

3:1+2

4:Starting

1/1

0

Disabled

●/●

●/●

5. 18.1

WXE

0302

Regenerative power ride-

through control

0:Deselect

1:Power ride-through
2:Deceleration stop during power failure
3:Synchronized deceleration/acceleration (synchronized

acceleration/deceleration signal)

4:Synchronized deceleration/acceleration (synchronized

acceleration/deceleration signal+power failure)

1/1

0

Disabled

●/●

-/-

5. 18. 2

RD

0304

Dynamic braking

selection

0:Deselect

1:Select (braking resistance overload detect)

2:Select (braking resistance overload not detect)

1/1

0

Disabled

●/●

●/●

5. 19

RDT

0308

Dynamic braking

resistance

0.5~1000Ω

0.1/0.1

*3

Disabled

●/●

●/●

5. 19

RDER

0309

Allowable continuous

braking resistance

0.01~600.0kW

0.01/0.01

*3

Disabled

●/●

●/●

5. 19

*1:

⇒ For the adjustment range, see the table on page K-39.

*2: For 200V-55/75kW models and 400V-90kW to 400V-280kW models, the carrier frequency is between 1.0 and 8.0kHz inclusive.

*3: Default values vary depending on the capacity.

⇒ See the table of K-46.

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)