Page 102

background image

E6581301

E-36

5

All 200V VF-AS1 and 400V VF-AS1 with ratings of up to 160kW have built-in dynamic braking resistors as standard
equipment. If the rating of your inverter falls within this range, connect the resistor, as shown in Figure a) below or
Figure b) on the next page. If your inverter has a power rating of 200kW or more, connect a resistor, as shown in
Figure c).

Connecting an external braking resistor (optional)

a) External braking resistor (with a thermal fuse) (optional)

IM

Motor

R/L1
S/L2
T/L3

U
V

W

Three-phase
main circuit
Power supply

PA/+

PB

MCCB

An external braking resistor
(optional)

Inverter

[Parameter setting]

Title

Function

Adjustment range

Example of setting

RD

Dynamic braking selection

:Deselect

:Select (bracking resistance

overload detect)

: Select (bracking resistance

overload not detect)

+

Do not connect an external resistor with a resistance (combined resistance) smaller than the minimum admissible

resistance.
For overload protection, be sure to set the parameters RDT and RDER properly.

[Parameter setting]

Title

Function

Adjustment range

Example of setting

RDT

Dynamic braking resistance

~Ω

Any value

RDER

Allowable continuous braking
resistance

~kW

Any value

H

Braking resistance overload
time

~ sec.

Set the parameter to

for type PBR*- or to

any value for other
types.