Toshiba Tosvert VF-AS1 User Manual
Page 169

E6581301
F-57
6
6.33.8 Control mode for low current
H
: Low current detection hysteresis width
H
: Low current trip selection
H
: Low current detection current
H
: Low current detection time
• Function
If the current is lower than H level and passes for a time longer than H, the inverter trips. When
tripping is selected, enter the detection time to tripping. Trip information is displayed as “WE.”
H
=: No tripping (Failure signal FL deactivated).
A low current alarm can be put out by setting the output terminal function selection parameter.
H
=: The inverter will trip (the failure signal FL will be activated) if a current below the current set with
H
flows for the period of time specified with H.
Title
Function
Adjustment range
Default setting
H
Low current detection hysteresis width
~%
H
Low current trip selection
: No trip
:Trip
H
Low current detection current
~%
H
Low current detection time
~ sec.
Output terminal function: 26 (UC) Low current detection
H
= (No trip)
Ex.) When outputting low current detection signals through output terminal OUT1
Title
Function
Adjustment range
Example of setting
H
Output terminal function selection 1(OUT1)
~
Note:To put out signals to the terminal OUT2, select the parameter H.
Time [sec]
H
+ H
H
Output current [%]
Low current
signal output
H
ON
OFF
OFF
less than
H
+
When H= (tripping), the inverter will trip if low current lasts for the period of time set with H.
After tripping, the low current signal remains ON.
6.33.9 Detection of output short circuit
H
: Selection of short circuit detection at starting
• Function
Detects a short-circuit on the output side of the inverter.
Title
Function
Adjustment range
Default setting
H
Selection of short circuit
detection at starting
:Each time (standard pulse)
:Only one time after power is turned on
:Each time (short pulse)
:Only one time after power is turn on (short pulse)
H
, : Standard —— detecting at starting
, : A check is made once at the first start of operation after the power is turned on or the
inverter is reset.
Note: When operating a high-speed motor, set H to . Any other setting may cause the motor to malfunction,
because a high-speed motor has a very low impedance.