E6581301

F-61

6

6.33.16 Regenerative power ride-through control level

H

: Regenerative power ride-through control level

• Function

This parameter is used to set the operation level of the regenerative power ride-through control and the
deceleration stop. (Refer to Section 5.18.2.)

Title

Function

Adjustment range

Default setting

H

Regenerative power ride-through control level

~%

Note: Set this parameter at a value of H+5% or more. Or the braking time of regenerative power ride-though

control could be extremely shorter. This setting is not necessary if H is set to (auto mode).

6.33.17 Braking answer waiting time

H

: Braking answer waiting time

• Function

This parameter is used to set the waiting time for answer from system (Input terminal function setting:
System supporting sequence (BA: Braking answer , )). After start of operation, if no answer is
received in set time (H), the inverter trips (G).

Title

Function

Adjustment range

Default setting

H

Braking answer waiting time

:Disabled

~ sec.

6.33.18 VI/II analog input wire breakage detection level

H

: VI/II analog input wire breakage detection level

• Function

The inverter will trip if the VI/II value remains below the specified value for 0.3 seconds or moreThe
message “G” is displayed.

H

=: Disabled

The detection function is disabled.

H

=~

The inverter will trip if the VI/II value remains below the specified value for 0.3

seconds or more.

Title

Function

Adjustment range

Default setting

H

VI/II analog input wire breakage detection level

:None

~%