8.2.2 Display of detailed information on a past trip

Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the

key when the

trip record is selected in the status monitor mode.
Unlike the " Monitor display at tripping " in 8.4.2, details on a past trip can be displayed, even after the inverter is turned off
or reset.

Item displayed

Key

operated

LED display

Description

Past trip 1

QE

⇔ Past trip 1 (displayed alternately.)

Continuous trips

P

The number of time the same trip occurred in succession is displayed.
(QEC, QEC, QEC, QEN Unit: times)

Output frequency

The operation frequency when the trip occurred is displayed.

Status monitor mode
(Rotating direction)

HTH

The direction of rotation is displayed. (H:Forward run, T:Reverse run)

Frequency command
value

The operation frequency command value is displayed.
(When H=, Frequency command)

Output current

E

The inverter output current (load current) is displayed.
(When H=, Output current)

Input voltage (DC
detection)

[

The inverter DC voltage is displayed. (Default setting unit:

)

(When H=, Input voltage) [Note 3]

Output voltage

R

The inverter output voltage is displayed. (Default setting unit:

)

(When H=, output voltage)

Input terminal
information

KKKKKKKK

The ON/OFF status of each of the control signal input terminals (F, R,
ST, RES, S1, S2, S3, RR/S4) is displayed in bits.

Output terminal
information

The ON/OFF status of each of the control signal output terminals
(OUT1, OUT2, FL) is displayed in bits.

Cumulative operation
time

V

The cumulative operation time when the trip occurred is displayed.
(0.01=1 hour, 1.00=100 hours)

Past trip 1

QE

⇔ Press this key to return to past trip 1.

Note 1: Press the

or

key to change items displayed in the status monitor mode.

Note 2: You can switch between % and A (ampere)/V (volt), using the parameter FURW (current/voltage unit selection).
Note 3: The input voltage displayed is 1/√2 times as large as the rectified DC input voltage.
Note 4: The number of bars displayed varies depending on the setting of H (logic output/pulse train output

selection). The bar representing the OUT1 terminal is displayed only when logic output function is assigned to it.

If H=

:The bar representing OUT1 is displayed.

If H=

:The bar representing OUT1 is not displayed.

Note 5: If there is no trip record, PGTT is displayed.

Note 6: The cumulative operation time increments only when the machine is in operation.

ENT

ENT

[Note 5]

[Note 1]

MODE

[Note 6]

[Note 4]

[Note 2]

[Note 2]
[Note 3]

[Note 2]