6.33.10 Overtorque trip
H
: Overtorque trip selection
H
: Overtorque detection level during power running
H
: Overtorque detection level during regenerative braking
H
: Overtorque detection time
H
: Overtorque detection hysteresis
• Function
Trips the inverter or issues an alarm if the total time for which torque is above the level set with
H
/H reaches the time set with H. Trip information is displayed as “QV.”
H
= (No trip)
No tripping (FL is not active).
H
= (Tripping)
The inverter will trip (the failure signal FL will be activated) if a torque larger than
H
(during power running) or H (during regeneration) passes for a time
longer than the time set with H.
Title
Function
Adjustment range
Default setting
H
Overtorque trip selection
:No trip
:Trip
H
Overtorque detection level during power running
~%
H
Overtorque detection level during regenerative braking
~%
H
Overtorque detection time
~ sec.
H
Overtorque detection hysteresis
~%
Note:Using the output terminal function selection parameter, the inverter can be set so that it outputs overtorque
detection signals regardless of the setting of H.
⇒ Refer to Section 7.2.2.
Output terminal function: 28 Overtorque detection
H
= (No trip)
Ex.) When outputting overtorque detection signals through output terminal OUT1
Title
Function
Adjustment range
Example of setting
H
Output terminal function selection 1(OUT1)
~
Note:To put out signals to the terminal OUT2, select the parameter H.
Time [sec]
H
- H
H
Torque [%]
Overtorque
signal output
H
ON
OFF
OFF
less than
H
When H= (tripping), the inverter will trip if overtorque lasts for the period of time set with H. In
such a case, the overtorque signal remains ON.