6.33.10 Overtorque trip

H

: Overtorque trip selection

H

: Overtorque detection level during power running

H

: Overtorque detection level during regenerative braking

H

: Overtorque detection time

H

: Overtorque detection hysteresis

• Function

Trips the inverter or issues an alarm if the total time for which torque is above the level set with
H

/H reaches the time set with H. Trip information is displayed as “QV.”

H

= (No trip)

No tripping (FL is not active).

H

= (Tripping)

The inverter will trip (the failure signal FL will be activated) if a torque larger than

H

(during power running) or H (during regeneration) passes for a time

longer than the time set with H.

Title

Function

Adjustment range

Default setting

H

Overtorque trip selection

:No trip

:Trip

H

Overtorque detection level during power running

~%

H

Overtorque detection level during regenerative braking

~%

H

Overtorque detection time

~ sec.

H

Overtorque detection hysteresis

~%

Note:Using the output terminal function selection parameter, the inverter can be set so that it outputs overtorque

detection signals regardless of the setting of H.

⇒ Refer to Section 7.2.2.


Output terminal function: 28 Overtorque detection

H

= (No trip)

Ex.) When outputting overtorque detection signals through output terminal OUT1

Title

Function

Adjustment range

Example of setting

H

Output terminal function selection 1(OUT1)

~

Note:To put out signals to the terminal OUT2, select the parameter H.

Time [sec]

H

- H

H

Torque [%]

Overtorque
signal output

H

ON

OFF

OFF

less than

H

When H= (tripping), the inverter will trip if overtorque lasts for the period of time set with H. In
such a case, the overtorque signal remains ON.