Toshiba Tosvert VF-AS1 User Manual
Page 86
E6581301
E-20
5
5.13
Selecting forward and reverse runs (operation panel only)
HT
: Forward/reverse run selection
[Parameter setting]
Title
Function
Adjustment range
Default setting
HT
Forward/reverse run selection
: Forward run
: Reverse run
: Forward run (F/R switching possible)
: Reverse run (F/R switching possible)
+
Check the direction of rotation on the status monitor.
HTH
: Forward run
HTT
: Reverse run
⇒ For monitoring, refer to Section 8.1.
+
When the F and R terminals are used for switching between forward run and stop from the terminal board, the HT
forward/reverse run selection parameter is rendered invalid.
Short across the F-CC terminals: forward run
Short across the R-CC terminals: reverse run
+
If F and CC, as well as R and CC are connected at the same time: Stop (Default setting)
Use the parameter H to select between reverse run and stop in this case.
⇒ For more details, refer to Section 6.2.1.
+
This function is valid only when EOQF is set at (Operation panel input enabled).
+
To switch between forward run and reverse run from the control panel with parameter HT set to or , perform
these steps: to switch to forward run, press the key while holding the key down, or to switch to reverse
run, press the key while holding key down.
• Function
Program the direction of rotation of the motor when the running and stopping are made using the RUN key and
STOP key on the operation panel.
Valid when EOQF (command mode selection) = (operation panel input).
ENT
ENT