Toshiba Tosvert VF-AS1 User Manual

Page 38

background image

E6581301

A-22

1

2.5kHz 4kHz

8kHz

12kHz

16kHz

Carrier frequency (EH)

200V 18.5~45kW (See lines shown in - - - for 22kW)
400V 22~75kW

100%

90%

80%

70%

60%

50%

Output cu

rrent

40°C:

(a)
When the upper protection cover is removed under
condition (a)
(b)

50°C:

(a)
When the upper protection cover is removed under
condition (a)
(b)

60°C:

(a)

When the upper protection cover is removed under
condition (a)
(b)

Ambient temperature: Permanently-installed inverters

400V

90~110kW

2.5kHz 3kHz 4kHz 5kHz 6kHz 7kHz

8kHz

Carrier frequency (EH)

100%

90%

80%

70%

60%

50%

40%

output cu

rrent

Ambient temperature: Permanently-installed inverters

50°C:

(a)
(b)

60°C:

(a)
(b)

400V 132kW or more

2.5kHz 3kHz 4kHz 5kHz 6kHz 7kHz

8kHz

Carrier frequency (EH)

100%

90%

80%

70%

60%

50%

40%

output cu

rrent

Ambient temperature: Permanently-installed inverters

50°C:

(a)
(b)

60°C:

(a)
(b)

40°C:

(a)
(b)

200V 55kW or more

2.5kHz 3kHz 4kHz 5kHz 6kHz 7kHz

8kHz

Carrier frequency (EH)

100%

90%

80%

70%

60%

50%

40%

output cu

rrent

Ambient temperature: Permanently-installed inverters

40°C:

(a)
(b)

50°C:

(a)
(b)

60°C:

(a)
(b)

+

The rated current indicated on the nameplate of a 15kW inverter or smaller is the current that flows at 4kHz. If the

carrier frequency is set at 12kHz by default, therefore, the rated current needs to be decreased.

For more details, refer to Section 12.

When H=, however, the carrier frequency decreases automatically with increase in current to secure the
rated current for frequencies below 4kHz.

+

Random control is exercised when the motor is operated in a low-frequency range where it produces annoying

magnetic noise.

+

If the carrier frequency control mode selection parameter (H) is set to or , the output voltage may drop.

The carrier frequency (EH) should be set below 4kHz.