3 increasing starting torque – Toshiba Tosvert VF-AS1 User Manual

Page 69

background image

E6581301

E-3

5

5.2.2 Manually setting acceleration/deceleration time

Set acceleration time from 0 (Hz) operation frequency to maximum frequency HJ and deceleration time as the time
when operation frequency goes from maximum frequency HJ to 0 (Hz).

Output frequency [Hz]

FGE

CEE

HJ

Time [s]

0

CW

= (Manual setting)

[Parameter setting]

Title

Function

Adjustment range

Default setting

CEE

Acceleration time 1

[Note]~ sec.

According to

model

FGE

Deceleration time 1

[Note]~ sec.

According to

model

Note:The minimum setting of acceleration and deceleration times have been set respectively at 0.1 sec. by default, but

they can be changed within a range of 0.01 sec. (setting range:0.01~600.0 sec.) by changing the setting of the
parameter V[R (default setting).
⇒ For details, refer to Section 5.20.

+

If the programmed value is shorter than the optimum acceleration/deceleration time determined by load conditions,
overcurrent stall or overvoltage stall function may make the acceleration/deceleration time longer than the
programmed time. If an even shorter acceleration/deceleration time is programmed, there may be an overcurrent
trip or overvoltage trip for inverter protection.
⇒ For details, refer to Section 13.1.

5.3

Increasing starting torque

CW

: Automatic torque boost

[Parameter setting]

Title

Function

Adjustment range

Default setting

CW

Automatic torque boost

: Deselect (Always is displayed.)

:Automatic torque boost+auto-tuning 1

: Sensorless vector control 1+auto-tuning 1

Note: Parameter displays on the right always return to after resetting. The previous setting is displayed on the

left.

Ex.

• Function

Simultaneously switches inverter output V/f control and programs motor constants automatically
(auto-tuning function 1) to improve torque generated by the motor.
This parameter integrates the
setting of special V/f control selection such as automatic torque boost or vector control.

{

Constant torque characteristics (default setting)

{

Automatic torque boost+auto-tuning 1

{

Sensorless vector control 1+auto-tuning 1

Note: Square reduction torque control, sensor vector control (optional), etc. can be selected using the V/f

control mode selection parameter RV.
⇒ For details, refer to Section 5.6.