3 description of terminals – Toshiba Tosvert VF-AS1 User Manual

Page 48

background image

E6581301

B-8

2

2.3

Description of terminals

2.3.1 Main circuit terminals

This diagram shows an example of wiring of the main circuit. Use options if necessary.

Power supply and motor connections

Power supply

S/L2 T/L3

Motor

No-fuse
breaker

Connect the power
cables to RL1, S/L2,
and T/L3.

Connect the motor
interconnect cables to
U/T1, V/T2 and W/T3.

VF-AS1

E

U/T1 V/T2 W/T3

R/L1

Connection with peripheral equipment

Motor

Zero-phase
reactor

Power
supply

Inverter

Braking resistor [Note]

Surge
suppressing filter

DC reactor

Simplified
radio noise
filter

High-attenuation
radio noise
reduction filter

Input AC
reactor

Magnetic
contactor

No-fuse
breaker

R/L1

S/L2

T/L3

PA/+ P0

PA/+ PB

V/T2

U/T1

W/T3

IM

Note: Connect a braking unit between

the terminals PA/+ and PC/-, if
necessary.

Main circuit

Terminal symbol

Terminal function

Grounding terminal for inverter casing

R/L1, S/L2, T/L3

200V class:

400V class:

0.4~45kW

Three-phase 200~240V-50/60Hz

0.75~75kW Three-phase 380~480V-50/60Hz

55kW, 75kW Three-phase 200~220V-50Hz

90~500kW

Three-phase 380~440V-50Hz

Three-phase 200~240V-60Hz

Three-phase 380~480V-60Hz

U/T1, V/T2, W/T3

Connect to a (3-phase induction) motor.

PA/+, PB

Connect a braking resistor. (For the optional dynamic braking unit, connect it between PA/+ and
PC/-.)
Change the parameters RD, RDT and RDER if necessary.
200kW models and larger are not equipped with terminal PB. If your are using such a model and
you wish to use a braking resistor, you will need to purchase a braking unit separately.

PC/-

This is a negative potential terminal in the internal DC main circuit. DC common power can be input
across the PA/+ terminals (positive potential).

PO, PA/+

Terminals for connecting a DC reactor (DCL: optional external device). Shorted by a short bar when
shipped from the factory (200V: 45kW or smaller, 400V: 75kW or smaller). Before installing DCL,
remove the short bar.

RO, SO, TO

200V class: 75kW

400V class:110kW~500kW

Inverter’s cooling power input terminals. When using a DC power supply, connect three-phase
power cables.