Setting acceleration/deceleration time

CW

: Automatic acceleration/deceleration

CEE

: Acceleration time 1

FGE

: Deceleration time 1

5.2.1 Automatic acceleration/deceleration

This automatically adjusts acceleration and deceleration time in line with load size.

CW =

* Adjusts the acceleration/deceleration time automatically within the range of 1/8 to 8 times as long as the time

set with the CEE or FGE, depending on the current rating of the inverter.

CW =

* Automatically adjusts speed during acceleration only. During deceleration, speed is not adjusted

automatically but reduced at the rate set with FGE.

Deceleration

Acceleration

HJ

When load is small

Time [s]

0

Deceleration

Acceleration

HJ

When load is large

Output

frequency [Hz]

Output

frequency [Hz]

Time [s]

0

Acceleration/deceleration time

decrease

Acceleration/deceleration time

increase

Set CW (automatic acceleration/deceleration) to or .

[Parameter setting]

Title

Function

Adjustment range

Default setting

CW

Automatic acceleration/deceleration

:Deselect (Manual setting)

:Automatic setting

:Automatic setting (during

acceleration only)

+

When automatically setting acceleration/deceleration time, always change the acceleration/deceleration time so that
it conforms with the load.
The acceleration/deceleration time changes constantly with load fluctuations.
For inverters that requires a fixed acceleration/deceleration time, use the manual settings (CEE, FGE).

+

When using a braking resistor or braking unit, do not set the CW=. Or the regenerative braking resistor may be
overloaded.

+

Use this parameter after actually connecting the motor.

+

Setting acceleration/deceleration time (CEE, FGE) in conformance with mean load allows optimum setting that
conforms to further changes in load.

+

When the inverter is used with a load that fluctuates considerably, it may fail to adjust the acceleration or
deceleration time in time, and therefore may be tripped.

• Function

1) For acceleration time 1 CEE programs the time that it takes for the inverter output frequency to go from

0Hz to maximum frequency HJ.

2) For deceleration time 1 FGE programs the time that it takes for the inverter output frequency to got from

maximum frequency HJ to 0Hz.