beautypg.com

20 pid control – Toshiba Tosvert VF-AS1 User Manual

Page 145

background image

E6581301

F-33

6

[Timing chart (example)]

Set frequency

Commercial power/inverter switching frequency

H

MC output for inverter operation
Commercial power/inverter switching output 1

(P24-OUT1)

MC output for commercial power operation
Commercial power/inverter switching output 2

(P24-OUT2)

Commercial power switching signal (S3-CC)

ON

Commercial power-side switching
waiting time H

Inverter-side switching waiting
time H

Detection time

Commercial power switching frequency
holding time H

ON

ON

ON

Operation standby signal (ST-CC)

ON

Commercial power switching signal S3-CC ON : Commercial power operation
Commercial power switching signal S3-CC OFF : Inverter operation
Note:If ST-CC is opened, switching cannot be operated normally.

Title

Function

Adjustment range

Example of setting

H

Commercial power/inverter switching output selection

~

or

H

Commercial power/inverter switching frequency

~WNHz

Power supply frequency etc.

H

Inverter-side switching waiting time

~ sec.

According to model

H

Commercial power-side switching waiting time

~ sec.

H

Commercial power switching frequency holding time

~ sec.

H

Input terminal function selection 7 (S3)

~

(Commercial power switching)

H

Output terminal function selection 1 (OUT1)

~

(Commercial power/inverter

switching output 1)

H

Output terminal function selection 2 (OUT2)

~

(Commercial power/inverter

switching output 2)

- Warning -
• When switching to commercial power, make sure that the direction in which the motor rotates when operated

on commercial power agrees with the forward direction when operated via the inverter.

• Do not select any option (H=) of H (reverse rotation prohibition selection) that prohibits forward

rotation. Or it becomes impossible to switch to commercial power, because the motor cannot rotate in the
forward direction.

6.20

PID control

H

:

PID control switching

H

: PID control feedback control signal selection

H

: Delay filter

H

: Proportional (P) gain

H

: Integral (I) gain

H

: PID deviation upper limit

H

: PID deviation lower limit

H

:

Differential (D) gain

H

: Process upper limit

H

: Process lower limit

H

: PID control waiting time

H

: PID output upper limit

H

: PID output lower limit

H

: Process increasing rate

(speed type PID control)

H

: Process decreasing rate

(speed type PID control)

⇒ For details, see Instruction Manual (E6581329) specified in Section 6.41.