Operation frequency

6.7.1 Start frequency

/Stop frequency

H

: Start frequency setting

H

: Stop frequency setting

• Function

The frequency set with the parameter H is put out as soon as operation is started.
Use the H parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a value from
0.5 to 2.0Hz (max. 5Hz) is recommended. The occurrence of an overcurrent can be suppressed by setting
this frequency below the rated slippage of the motor. If 0 speed torque is needed (RV=, ), set H,
H

at 0.0Hz.

• At start up : frequency set with H is put out immediately.
• At stop

: The output frequency drops to 0Hz immediately by the frequency set with H.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Starting frequency setting

~Hz

H

Stop frequency setting

~Hz

Start frequency setting

H

Stop frequency setting

H

Output frequency [Hz]

Time [s]

0

Note: Set these parameters so that the start frequency H is higher than the stop frequency H .

If the H -set frequsency is lower than the H -set frequency, the reference frequency must be
higher than the H-set frequency to start the motor.
If both H and H are set to Hz, the motor will start even if the frequency set is 0.0Hz.

6.7.2 Run

/Stop control with frequency setting signals

H

: Operation start frequency

H

: Operation start frequency hysteresis

• Function

The Run/Stop of operation can be controlled simply with frequency setting signals.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Operation starting frequency

~HJ

H

Operation starting frequency hysteresis

~Hz