E6581301

F-16

6

[Priority to DC braking during forward/reverse operation] (Forward/reverse run DC braking priority control H=[ON])

Time [s]

H

H

Output frequency [Hz]

Forward run signal (F-CC)

ON
OFF

Reference frequency

0

0

Set frequency

~

~

~

~

~

~

~

~

H

H

: DC braking

H

H

(4)

(5)

(6)

Reverse run signal (R-CC)

ON
OFF

H

H=

H=

H

(7)

(4) During normal forward/reverse run (H=)

: Not recognized as a stop command, so that the DC

braking is not active.

(5) If a reverse run (or forward) command is entered during forward run (or reverse) (H=) :

DC braking when the frequency set with H
decreases below the reference frequency during
deceleration.

(6) If an operation command is entered during DC braking : RUN command has a priority.
(7) If an operation command is changed from ON to OFF during DC braking, DC braking is discontinued to stop the

operation.

6.8.2 Motor shaft fixing control

H

: Motor shaft fixing control

• Function

This function is used to prevent the motor from running unexpectedly after the motor is stopped because
it’s shaft is not restrained or to preheat the motor.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Motor shaft fixing control

:Disabled, :Enabled

If the motor shaft fixing control parameter H is set at , DC braking continue at half a braking rate of that set with
H

to retain the motor after it has come to a full stop by DC braking. To terminate the motor shaft fixing control cut

off the standby signal (ST signal). Note, however, that this function doesn't operate after a DC braking command is
entered by control input terminal signal.