beautypg.com

Toshiba Tosvert VF-AS1 User Manual

Page 255

background image

K-17

E6581301

11

[19] Torque control [2/2]

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control V/f Constant Reference

H

0425

Forward speed limit input

selection

0:Disabled

1:VI/II (voltage/current input)

2:RR/S4 (potentiometer/voltage input)

3:RX (voltage input)

4:H enabled

1/1

0

Enabled

-

●/●

-

-

*1

H

0426

Forward speed limit input level

0.0~WN Hz

0.1/0.01

*2

Enabled

-

●/●

-

-

*1

H

0427

Reverse speed limit input

selection

0:Disabled

1:VI/II (voltage/current input)

2:RR/S4 (potentiometer/voltage input)

3:RX (voltage input)

4:H enabled

1/1

0

Enabled

-

●/●

-

-

*1

H

0428

Reverse speed limit input level

0.0~WN Hz

0.1/0.01

*2

Enabled

-

●/●

-

-

*1

H

0430

Speed limit (torque = 0) center

value reference selection

0:Disabled, 1:VI/II (voltage/current input)

2:RR/S4 (potentiometer/voltage input)

3:RX (voltage input), 4:H enabled

1/1

0

Enabled

-

●/●

-

-

*1

H

0431

Speed limit (torque = 0) center

value

0.0~HJ Hz

0.1/0.01

0.0

Enabled

-

●/●

-

-

*1

H

0432

Speed limit (torque = 0) band

0.0~HJ Hz

0.1/0.01

0.0

Enabled

-

●/●

-

-

*1

H

0435

Prohibition of rotation in any

direction other than the specified

one (F or R)

0:Disabled

1:Enabled

1/1

0

Enabled

-

●/●

-

-

*1

*1:

⇒ For details, refer to Instruction Manual (E6581331) specified in Section 6.41. *2: Inverter with a model number ending with -WN: 60.0 -WP: 50.0

[20] Torque limit [1/2]

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control V/f Constant Reference

H

0440

Power running torque limit 1

selection

1:VI/II (voltage/current input)

2:RR/S4 (potentiometer/voltage input)

3:RX (voltage input)

4:H

1/1

4

Enabled

●/●

●/●

-

6. 25. 1

H

0441

Power running torque limit 1

level

0:0~249.9%, 250.0:Disabled

0.1/0.01

250.0

Enabled

●/●

●/●

-

6. 25. 1

H

0442

Regenerative braking torque

limit 1 selection

1:VI/II (voltage/current input)

2:RR/S4 (potentiometer/voltage input)

3:RX (voltage input)

4:H

1/1

4

Enabled

●/●

●/●

-

6. 25. 1

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)