3 terminal function selection – Toshiba Tosvert VF-AS1 User Manual

Page 118

background image

E6581301

F-6

6

6.3

Terminal function selection

6.3.1 Keeping an input terminal function always active (ON)

H

, H , H

: Always ON function selection 1~3

• Function

This parameter specifies an input terminal function that is always kept active (ON). (Only one function
selectable)

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Always ON function selection 1

~

H

Always ON function selection 2

~

H

Always ON function selection 3

~

* The selected function is always kept active regardless of the type of logic (positive or negative) in the table of

function settings in 7.2.1.

6.3.2 Modifying input terminal functions

H

: Input terminal function selection 1 (F)

H

: Input terminal function selection 2 (R)

H

: Input terminal function selection 3 (ST)

H

: Input terminal function selection 4 (RES)

H

: Input terminal function selection 5 (S1)

H

: Input terminal function selection 6 (S2)

H

: Input terminal function selection 7 (S3)

H

: Input terminal function selection 8 (RR/S4)

H

~ H :

Input terminal function selection 9~16

H

~ H :

Input terminal function selection 17~20

⇒ For details, refer to Section 7.2.1.

• Function

Use the above parameters to send signals from an external programmable controller to various control input
terminals to operate and/or set the inverter.
The desired contact input terminal functions can be selected from 120 types (-). This gives system
design flexibility.
Using the SW3 switch, the function of the RR/S4 terminal can be selected between analog input and contact
input. By default, the RR/S4 terminal is set as an analog input terminal (voltage input terminal). To use it as a
contact input terminal, therefore, you need to turn the SW3 switch to the S4 position.

Setting of contact input terminal function

Terminal

symbol

Title

Function

Adjustment range

Default

setting

H

, H, H

Always ON function selection 1~3

F

H

Input terminal function selection 1 (F)

(F)

R

H

Input terminal function selection 2
(R)

(R)

ST

H

Input terminal function selection 3
(ST)

(ST)

RES

H

Input terminal function selection 4
(RES)

(RES)

S1

H

Input terminal function selection 5
(S1)

(S1)

S2

H

Input terminal function selection 6
(S2)

(S2)

S3

H

Input terminal function selection 7
(S3)

~

(

⇒ Refer to Section 11.)

(S3)

The terminal below is operative only when SW3 is in the S4 position.

RR/S4

H

Input terminal function selection 7
(S4)

~ [Note 2]

(S4)

Note 1: The function that has been selected using H, Hand H (always ON function selection 1~3

parameter) are always activated.

Note 2: When using the RR/R4 terminal as a contact input terminal (sink logic), always turn the SW3 slide switch to

the S4 position.