30 acceleration/deceleration 2 – Toshiba Tosvert VF-AS1 User Manual
Page 160
E6581301
F-48
6
6.30
Acceleration/deceleration 2
6.30.1 Setting acceleration/deceleration patterns and switching
acceleration/deceleration patterns 1, 2, 3 and 4
H
: Acceleration time 2
H
: Deceleration time 2
H
: Acceleration/deceleration 1 pattern
H
: Acceleration/deceleration 2 pattern
H
: Acceleration/deceleration time 1, 2, 3, 4 selection
H
: Acceleration/deceleration switching frequency 1
H
: Acceleration S-pattern lower limit adjustment
H
: Acceleration S-pattern upper limit adjustment
H
: Deceleration S-pattern lower limit adjustment
H
: Deceleration S-pattern upper limit adjustment
H
: Acceleration time 3
H
: Deceleration time 3
H
: Acceleration/deceleration 3 pattern
H
: Acceleration/deceleration switching frequency 2
H
: Acceleration time 4
H
: Deceleration time 4
H
: Acceleration/deceleration 4 pattern
H
: Acceleration/deceleration switching frequency 3
• Function
Four acceleration times and four deceleration times can be specified individually. The selection/switching
mode can be selected from the following 3 options:
1) Selection by means of parameters
2) Switching by means of frequencies
3) Switching by means of terminals
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Acceleration time 2
[Note]~ sec.
According to model
H
Deceleration time 2
[Note]~ sec.
According to model
H
Acceleration/deceleration 1, 2, 3,
4 selection
:Acceleration/deceleration 1,
: Acceleration/deceleration 2,
: Acceleration/deceleration 3,
: Acceleration/deceleration 4
H
Acceleration time 3
[Note]~ sec.
According to model
H
Deceleration time 3
[Note]~ sec.
According to model
H
Acceleration time 4
[Note]~ sec.
According to model
H
Deceleration time 4
[Note]~ sec.
According to model
Note:The minimum setting of acceleration and deceleration times have been set respectively at 0.1 sec. by default,
but they can be changed within a range of 0.01 sec. (setting range:0.01~600.0 sec.) by changing the setting of
the parameter V[R (default setting).
⇒ For details, refer to Section 5.20.
1) Selection using parameters
Time [s]
Output frequency [Hz]
FGE
CEE
HJ
H
H
H
H
H
H
0
Time [s]
Time [s]
Time [s]
H
=
H
=
H
=
H
=
Acceleration/deceleration time 1 is initially set as the default. Acceleration/deceleration time 2, 3 and 4can be
selected by changing the setting of the H.
Enabled if EOQF= (operation panel input enabled).