4) Setting the frequency using input voltage (0~10Vdc)

[Parameter setting]

5) Setting the frequency using input voltage (0~±10Vdc)

The direction can be changed by switching between positive and negative signals.

[Parameter setting]

Set the “basic parameter frequency setting mode selection 1” parameter

HOQF to .

Note: Set reference frequency priority selection H to (HOQF/H terminal switching, default setting).

Changing the settings of two speed command parameters at a time, refer to Section 6.6.

[Example of setting: To set the frequency by applying a current of 4(0)-20mAdc via the VI/II terminal.]

Key operated

LED display

Operation

Displays the operation frequency. (Perform during operation stopped.)
(When standard monitor display selection H=[Output
frequency])

CWJ

Displays the first basic parameter “History function (CWJ).”

HOQF

Press either the or key to select “HOQF.”

Press the ENTER key to display the parameter setting (Default
setting:).

Press the key to change the parameter to .

⇔HOQF

Press the ENTER key to save the changed parameter. HOQF and the
parameter are displayed alternately.

MODE

Frequency

0

0Vdc

10Vdc

60Hz

Set the “extended parameter analog input VI/II voltage/current switching”
parameter HOQF to .
In addition, set the “basic parameter frequency setting mode selection 1” parameter
H

to (default setting

)

.

+

-

RX

CCA

-10Vdc

+10Vdc

Forward run

Reverse run

60Hz

60Hz

+

-

ENT

ENT

VI/II

CCA

+

Voltage signal

Voltage signal (0~10V) for setting the operation frequency
⇒ Refer to Section 7.3 for details of adjustment.

:Voltage signal 0-10Vdc

+

Voltage signal

Voltage signal (0~±10V) for setting the operation frequency
⇒ Refer to Section 7.3 for details of adjustment.

:Voltage signal 0-±10Vdc