Toshiba Tosvert VF-AS1 User Manual
Page 264
K-26
E6581301
11
[27] Operation panel parameters [1/3]
Vector control
Title
Communi
cation
No.
Function
Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control V/f Constant Reference
H
0700
Parameter write protect
selection
0:Permit, 1:Prohibit
1/1
0
Enabled
●/●
●/●
●
●
6. 36. 1
FURW
0701
Current/voltage unit selection
0:%, 1:A (ampere)/V (volt)
1/1
0
Enabled
●/●
●/●
●
●
5. 15
H
0702
Frequency free unit display
magnification
0.00:OFF, 0.01~200.0
0.01/0.01
0.00
Enabled
●/●
●/●
●
●
6. 36. 2
H
0703
Frequency free unit conversion
selection
0:All frequencies display free unit conversion
1:PID frequencies free unit conversion
1/1
0
Enabled
●/●
●/●
●
●
6. 36. 2
H
0705
Free unit display gradient
characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1
Enabled
●/●
●/●
●
●
6. 36. 2
H
0706
Free unit display bias
0.00~HJ Hz
0.01/0.01
0.00
Enabled
●/●
●/●
●
●
6. 36. 2
H
0707
Changing step selection 1
0.00:Disabled, 0.01~HJ Hz
0.01/0.01
0.00
Enabled
●/●
●/●
●
●
6. 36. 3
H
0708
Changing step selection 2
0:Disabled, 1~255
1/1
0
Enabled
●/●
●/●
●
●
6. 36. 3
H
0709
Standard monitor hold function
0:Real time, 1:Peak hold, 2:Minimum hold
1/1
0
Enabled
●/●
●/●
●
●
8. 3
H
0710
Standard monitor display
selection
0~70 *1
1/1
0
Enabled
●/●
●/●
●
●
8. 3
H
0711
Status monitor 1 display
selection
Ditto
1/1
1
Enabled
●/●
●/●
●
●
8. 3
H
0712
Status monitor 2 display
selection
Ditto
1/1
2
Enabled
●/●
●/●
●
●
8. 3
H
0713
Status monitor 3 display
selection
Ditto
1/1
3
Enabled
●/●
●/●
●
●
8. 3
H
0714
Status monitor 4 display
selection
Ditto
1/1
4
Enabled
●/●
●/●
●
●
8. 3
H
0715
Status monitor 5 display
selection
Ditto
1/1
8
Enabled
●/●
●/●
●
●
8. 3
H
0716
Status monitor 6 display
selection
Ditto
1/1
16
Enabled
●/●
●/●
●
●
8. 3
H
0717
Status monitor 7 display
selection
Ditto
1/1
15
Enabled
●/●
●/●
●
●
8. 3
H
0718
Status monitor 8 display
selection
Ditto
1/1
14
Enabled
●/●
●/●
●
●
8. 3
H
0719
Operation command clear
selection when standby terminal
(ST) is OFF
0:Clear operation command, 1:Retain operation
command
1/1
1
Enabled
●/●
●/●
●
●
6. 36. 5
H
0721
Operation panel stop pattern
0:Deceleration stop, 1:Coasting
1/1
0
Enabled
●/●
●/●
●
●
6. 36. 6
H
0725
Operation panel torque
command
-250~250%
1/0.01
0
Enabled
-
●/●
-
-
6. 36. 7
H
0727
Operation panel tension torque
bias
-250~250%
1/0.01
0
Enabled
-
●/●
-
-
6. 36. 8
H
0728
Operation panel load sharing
gain
0~250%
1/0.01
100
Enabled
-
●/●
-
-
6. 36. 8
H
0729
Operation panel override
multiplication gain
-100~100%
1/0.01
0
Enabled
●/●
-
●
●
6. 34
H
0730
Operation panel frequency
setting prohibition selection
0:Permit
1:Prohibit
1/1
0
Enabled
●/●
●/●
●
●
6. 36. 1
This parameter moves to a fundamental parameter. *1:
⇒ For the adjustment range, see the table on page K-39.
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)