[27] Operation panel parameters [1/3]

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control V/f Constant Reference

H

0700

Parameter write protect

selection

0:Permit, 1:Prohibit

1/1

0

Enabled

●/●

●/●

6. 36. 1

FURW

0701

Current/voltage unit selection

0:%, 1:A (ampere)/V (volt)

1/1

0

Enabled

●/●

●/●

5. 15

H

0702

Frequency free unit display

magnification

0.00:OFF, 0.01~200.0

0.01/0.01

0.00

Enabled

●/●

●/●

6. 36. 2

H

0703

Frequency free unit conversion

selection

0:All frequencies display free unit conversion

1:PID frequencies free unit conversion

1/1

0

Enabled

●/●

●/●

6. 36. 2

H

0705

Free unit display gradient

characteristic

0:Negative inclination (downward slope)

1:Positive inclination (upward slope)

1/1

Enabled

●/●

●/●

6. 36. 2

H

0706

Free unit display bias

0.00~HJ Hz

0.01/0.01

0.00

Enabled

●/●

●/●

6. 36. 2

H

0707

Changing step selection 1

0.00:Disabled, 0.01~HJ Hz

0.01/0.01

0.00

Enabled

●/●

●/●

6. 36. 3

H

0708

Changing step selection 2

0:Disabled, 1~255

1/1

0

Enabled

●/●

●/●

6. 36. 3

H

0709

Standard monitor hold function

0:Real time, 1:Peak hold, 2:Minimum hold

1/1

0

Enabled

●/●

●/●

8. 3

H

0710

Standard monitor display

selection

0~70 *1

1/1

0

Enabled

●/●

●/●

8. 3

H

0711

Status monitor 1 display

selection

Ditto

1/1

1

Enabled

●/●

●/●

8. 3

H

0712

Status monitor 2 display

selection

Ditto

1/1

2

Enabled

●/●

●/●

8. 3

H

0713

Status monitor 3 display

selection

Ditto

1/1

3

Enabled

●/●

●/●

8. 3

H

0714

Status monitor 4 display

selection

Ditto

1/1

4

Enabled

●/●

●/●

8. 3

H

0715

Status monitor 5 display

selection

Ditto

1/1

8

Enabled

●/●

●/●

8. 3

H

0716

Status monitor 6 display

selection

Ditto

1/1

16

Enabled

●/●

●/●

8. 3

H

0717

Status monitor 7 display

selection

Ditto

1/1

15

Enabled

●/●

●/●

8. 3

H

0718

Status monitor 8 display

selection

Ditto

1/1

14

Enabled

●/●

●/●

8. 3

H

0719

Operation command clear

selection when standby terminal

(ST) is OFF

0:Clear operation command, 1:Retain operation

command

1/1

1

Enabled

●/●

●/●

6. 36. 5

H

0721

Operation panel stop pattern

0:Deceleration stop, 1:Coasting

1/1

0

Enabled

●/●

●/●

6. 36. 6

H

0725

Operation panel torque

command

-250~250%

1/0.01

0

Enabled

-

●/●

-

-

6. 36. 7

H

0727

Operation panel tension torque

bias

-250~250%

1/0.01

0

Enabled

-

●/●

-

-

6. 36. 8

H

0728

Operation panel load sharing

gain

0~250%

1/0.01

100

Enabled

-

●/●

-

-

6. 36. 8

H

0729

Operation panel override

multiplication gain

-100~100%

1/0.01

0

Enabled

●/●

-

6. 34

H

0730

Operation panel frequency

setting prohibition selection

0:Permit

1:Prohibit

1/1

0

Enabled

●/●

●/●

6. 36. 1

This parameter moves to a fundamental parameter. *1:

⇒ For the adjustment range, see the table on page K-39.

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)