beautypg.com

2 monitoring the status, Twice – Toshiba Tosvert VF-AS1 User Manual

Page 210

background image

E6581301

H-2

8

8.2

Monitoring the status

8.2.1 Status monitor under normal conditions

In this mode, you can monitor the operation status of the inverter.

To monitor the inverter when it is normally running, press the

key

twice

and the current status is indicated

on the LED display.

Setting procedure (EX.: operation at 60 Hz)

Commun

ication

No.

Item displayed

Key

operated

LED

display

Description

-

Standard monitor
mode

The operation frequency is displayed (during operation).
(When standard monitor display selection H is set
to [Output frequency])

FE01

Setting monitor
mode

CWJ

The first basic parameter “History function (CWJ)” is
displayed.

FE01

Status monitor mode
(Rotating direction)

HTH

The rotating direction is displayed. (H:Forward run,
T

:Reverse run)

-

Frequency
command value

The operation frequency command value is displayed.
(When H=, Frequency command)

-

Output current

E

The inverter output current (load current) is displayed.
(When H=, Output current)

-

Input voltage (DC
detection)

[

The Inverter DC voltage (default setting:unit %) is
displayed.(When H=, Input voltage) [Note 3]

-

Output voltage

R

The inverter output voltage (default setting:unit %) is
displayed.(When H=, output voltage)

-

Torque

S

The torque is displayed.
(When H= torque)

-

Regenerative
braking resistance
overload factor
(PBrOL data)

T

The regenerative braking resistance overload factor is
displayed.
(When H=, regenerative braking resistance
overload factor)

-

Inverter overload
factor
(OL1 data)

I

The inverter overload factor is displayed.
(When H=, inverter overload factor)

-

Motor overload
factor

E

The motor overload factor (default setting:unit %) is
displayed.
(When H=, Motor overload factor)

Input terminal
information 1

The ON/OFF status of each of the control signal input
terminals (F, R, ST, RES, S1, S2, S3, RR/S4) is
displayed in bits.

Input terminal
information 2

C

The ON/OFF status of each of the optional control signal
input terminals (LI1, LI2, LI3, LI4) is displayed in bits.

FE06

Input terminal
information 3

D

The ON/OFF status of each of the optional control signal
input terminals (LI5, LI6, LI7, LI8) is displayed in bits.

Output terminal
information 1

The ON/OFF status of each of the control signal output
terminals (OUT1, OUT2, FL) is displayed in bits.

FE07

Output terminal
information 2

The ON/OFF status of each of the optional control signal
output terminals (OUT3, OUT4, R1, OUT5, OUT6, R2,
R3, R4) is displayed in bits.

FE08

CPU1 version

X

The version of the CPU1 is displayed.

FE73

CPU2 version

Y

The version of the CPU2 is displayed.

(Continued overleaf)

*1

MODE

*2

*3

*4

MODE

*5

*7

*8

*9

*6

MODE

[Note 4]