7.3.2 Setup by analog input signals (VI/II terminal)

Connect current signal (4 (0) to 20mAdc) or voltage signal (0 to 10Vdc) to the terminal II so that the inverter can be run
and stopped with external commands.

Example of setting

Title

Function

Adjustment

range

Default setting

4 (0)~20mAdc

0~10Vdc

EOQF

Command mode selection

~

(Terminal)

(Terminal)

(Terminal)

HOQF

Frequency setting mode selection 1

~

(RR/S4)

(VI/II)

(VI/II)

HOUN

FM terminal meter selection

~

HO

FM terminal meter adjustment

-

-

-

-

H

Analog VI/VII voltage/current switching

: Voltage input

: Current input

H

Frequency priority selection

,

H

VI/II input point 1 setting

~%

H

VI/II input point 1 frequency

~HJ Hz

H

VI/II input point 2 setting

~%

CKH

VI/II input point 2 frequency

~HJ Hz

*1

*1

*1

H

Analog input filter

(No filter)~

(Max. filter)

*1:

Inverter with a model number ending with -WN: 60.0 -WP: 50.0

Run/stop setup
To control switching between forward run
(F) and reverse run (R), run and stop by
external commands.

Setup of frequency setting signal and
running frequency characteristic
To set up frequency setting signal to be
input to the external signal (VI/II terminal)
and characteristic of running frequency.
Frequency characteristic is set up at the
two points of VI/II reference point 1
(H)/frequency (H), VI/II
reference point 2 (H)/frequency
(CKH).

Connection and calibration of
frequency meter
Connect a 1mAdc full-scale DC current
meter, 7.5Vdc full-scale DC voltmeter or
rectifier type AC voltmeter. For calibration
of the meter, refer to the Section 5.16.

Hz

%

CKH

H

H

H

Point 2

Point 1

Frequency setting signal

 

0% 20%  100%

(0 ~ 4  ~  20mA) current input

(0     ~   10V ) voltage input

Operation
frequency

*4(0)~20mAdc

or 0~10Vdc

+

-

+

To apply a current through the VI/II terminal, the

setting of H needs to be changed.

Motor

R/L1

U/T1

MCCB

Power

supply

S/L2
T/L3

V/T2

W/T3

CCA RX

RES

S1

S2

CC

S3

F

R

ST

FM

AM

FLA

FLB

FLC

P24/PLC

OUT1

OUT2

VI/II

PP

VF-AS1

CHARGE

Forward run

Reverse run

Frequency

meter

NO

CC

RR/S4

IM