beautypg.com

Toshiba Tosvert VF-AS1 User Manual

Page 243

background image

K-5

E6581301

11

2. Extended parameters

[1] Frequency signal

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control

V/f

Reference

H

0100

Low-speed signal output

frequency

0.0~WN Hz

0.1/0.01

0.0

Enabled

●/●

●/●

6. 1. 1

H

0101

Speed reach setting

frequency

0.0~WN Hz

0.1/0.01

0.0

Enabled

●/●

●/●

6. 1. 2

H

0102

Speed reach detection

band

0.0~WN Hz

0.1/0.01

2.5

Enabled

●/●

●/●

6. 1. 2

[2] Input signal selection

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control

V/f

Reference

H

0105

Priority when

forward/reverse run

commands are entered

simultaneously

0:Reverse run, 1:Stop

1/1

1

Disabled

●/●

●/●

6. 2. 1

H

0106

Input terminal priority

selection

0:Deselect, 1:Select

1/1

0

Disabled

●/●

●/●

6. 2. 2

H

0107

16-bit binary/BCD input

selection

0:Deselect

1:12-bit binary input

2:16-bit binary input

3:3-digit BCD input

4:4-digit BCD input

5:12-bit binary input inverse

6:16-bit binary input inverse

7:3-digit BCD input inverse

8:4-digit BCD input inverse

1/1

0

Disabled

●/●

●/●

6. 2. 3

H

0108

Analog VI/VII

voltage/current switching

0:Voltage input

1:Current input

1/1

0

Disabled

●/●

-/-

6. 2. 4

H

0109

Analog AI2 (optional

circuit board)

voltage/current switching

0:Voltage input

1:Current input

1/1

0

Disabled

●/●

-/-

6. 2. 4

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)