Toshiba Tosvert VF-AS1 User Manual
Page 245

K-7
E6581301
11
[4] Terminal response time setup
Vector control
Title
Communi
cation
No.
Function
Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f
Reference
H
0140
Input terminal 1 response time
selection (F)
2~200ms
1/1
8
Disabled
●/●
●/●
●
●
7. 2. 3
H
0141
Input terminal 2 response time
selection (R)
2~200ms
1/1
8
Disabled
●/●
●/●
●
●
7. 2. 3
H
0142
Input terminal 3 response time
selection (ST)
2~200ms
1/1
8
Disabled
●/●
●/●
●
●
7. 2. 3
H
0143
Input terminal 4 response time
selection (RES)
2~200ms
1/1
8
Disabled
●/●
●/●
●
●
7. 2. 3
H
0144
Input terminal 5~12 response
time selection
2~200ms
1/1
8
Disabled
●/●
●/●
●
●
7. 2. 3
H
0145
Input terminal 13~20 response
time selection
5~200ms
1/1
8
Disabled
●/●
●/●
●
●
7. 2. 3
H
0164
Input terminal selection 17(B12) 0~135 *1
1/1
0
Disabled
●/●
●/●
●
●
7. 2. 1
H
0165
Input terminal selection 18(B13) 0~135 *1
1/1
0
Disabled
●/●
●/●
●
●
7. 2. 1
H
0166
Input terminal selection 19(B14) 0~135 *1
1/1
0
Disabled
●/●
●/●
●
●
7. 2. 1
H
0167
Input terminal selection 20(B15) 0~135 *1
1/1
0
Disabled
●/●
●/●
●
●
7. 2. 1
H
0168
Output terminal function
selection 10 (R3)
0~255 *2
1/1
254
Disabled
●/●
●/●
●
●
7. 2. 2
H
0169
Output terminal function
selection 11 (R4)
0~255 *2
1/1
254
Disabled
●/●
●/●
●
●
7. 2. 2
H
0170
Base frequency 2
25.0~HJ Hz
0.1/0.01
*4
Disabled
-
-
●
●
6. 4. 1
H
0171
Base frequency voltage 2
50~330V/660V
1/0.1
*3
Disabled
-
-
●
●
6. 4. 1
H
0172
Manual torque boost 2
0.0~30.0%
0.1/0.1
*3
Enabled
-
-
●
●
6. 4. 1
H
0173
Motor overload protection level
2
10~100%
1/1
100
Enabled
-
-
●
●
6. 4. 1
H
0174
Base frequency 3
25.0~HJ Hz
0.1/0.01
*4
Disabled
-
-
●
●
6. 4. 1
H
0175
Base frequency voltage 3
50~330V/660V
1/0.1
*3
Disabled
-
-
●
●
6. 4. 1
H
0176
Manual torque boost 3
0.0~30.0%
0.1/0.1
*3
Enabled
-
-
●
●
6. 4. 1
H
0177
Motor overload protection level
3
10~100%
1/1
100
Enabled
-
-
●
●
6. 4. 1
H
0178
Base frequency 4
25.0~HJ Hz
0.1/0.01
*4
Disabled
-
-
●
●
6. 4. 1
H
0179
Base frequency voltage 4
50~330V/660V
1/0.1
*3
Disabled
-
-
●
●
6. 4. 1
H
0180
Manual torque boost 4
0.0~30.0%
0.1/0.1
*3
Enabled
-
-
●
●
6. 4. 1
H
0181
Motor overload protection level 4
10~100%
1/1
100
Enabled
-
-
●
●
6. 4. 1
*1:
⇒ For the adjustment range, see the table on page K-41.
*2:
⇒ For the adjustment range, see the table on page K-43.
*3: Default values vary depending on the capacity.
⇒ See the table of K-46.
*4: Inverter with a model number ending with -WN: 60.0 -WP: 50.0
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)