Toshiba Tosvert VF-AS1 User Manual
Page 178
E6581301
F-66
6
6.35.2 Setting of optional meter outputs
H
~ H , H ~ H : Meter output settings
⇒ For details, refer to Instruction Manual (E6581341) specified in Section 6.41.
6.35.3 Calibration of analog outputs
H
: FM voltage/current output switching
H
, H : FM output gradient characteristic and bias adjustment
H
, H : AM output gradient characteristic and bias adjustment
•Function
Output signals from FM/AM terminals are analog voltage signals. Their standard setting range is from 0 to
10Vdc.
The output current from terminal FM can be changed to 0 to 20mAdc (or 4 to 20mAdc) by changing the settings
of terminal SW2 and a parameter.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
FM voltage/current output
switching
: Voltage 0~10V output
: Current 0~20mA output
H
FM output gradient
characteristic
: Negative gradient
(descending)
: Positive gradient (ascending)
H
FM bias adjustment
- .%
H
AM output gradient
characteristic
: Negative gradient
(descending)
: Positive gradient (ascending)
H
AM bias adjustment
- .%
Note: To switch to 0-20mAdc (4-20mAdc), set H to .
■
FM terminals setting example
SW2=OFFH, H= H= (%)
SW2=OFFH, H= H= (%)
20
0
0
Internal calculated value
100%
0
Internal calculated value
100%
HO
HO
4
O
utpu
t cu
rr
ent
(mA)
20
O
utpu
t cu
rre
nt
(mA)
H
SW2=OFFH= H= H= (%)
SW2=OFFH= H= H=(%)
20
0
0
Internal calculated value
100%
0
100%
HO
: Large gain
HO
:Small gain
4
O
utput
cu
rre
nt
(mA)
20
Ou
tput cu
rre
nt
(mA
H
H
Internal calculated value
+
The analog output inclination can be adjusted using the parameter HO
+
For code data 50 to 64, negative inclination is invalid.