Toshiba 4200FA Series User Manual
Ries, 4200 fa se, Extended extended
4200FA Se
ries
ß
True On-Line Double Conversion UPS
ß
Input Power Factor > 0.99
ß
Input Current THD < 3%
ß
Wide Input Voltage Window +20% to -30%
ß
Wide Input Frequency Window 45 to 65 Hz
ß
All IGBT 12 kHz Design (Rectifier/DC Converter/Inverter)
ß
Electronic Power Factor Correction for 100% Generator Compatibility
ß
Complete Front Access for Installation, Operation, and Service
ß
External Battery Options for Customized Battery Back-Up Time
ß
XT Series is Designed for Extreme Applications
ß
Internal Isolation Transformer(s)
ß
Internal Maintenance Bypass Switch*
ß
100% Unbalanced Load Capability
ß
SNMP/Web-Based Monitoring
15/25/30/50/80 kVA UPS
���������
��������
���������
Extended
Warranty
Available
���������
Extended
Extended
���������
UNINTERRUPTIBLE POWER SYSTEMS
- Power Inverter (15 pages)
- 1800 (6 pages)
- TOSVERT VF-S11 (68 pages)
- Uninterruptible Power System G9000 (104 pages)
- Density (Consistency) Meter LQ500 (9 pages)
- MBSB80-225-43 (1 page)
- TOSNIC-7000S (53 pages)
- 1600EP Series (3 pages)
- 1500 (32 pages)
- TOSVERT VF-FS1 Series (16 pages)
- 4200FA XT1 (1 page)
- G3 Plus Pack (4 pages)
- Tosvert VF-A5 (149 pages)
- 1600 Series (3 pages)
- G9000 (100 pages)
- TEC EO1-33030 (54 pages)
- 1000 Series (2 pages)
- 1500 Plus (31 pages)
- G8000MM (6 pages)
- VT130G1 (99 pages)
- VF-PS1 (10 pages)
- GX7 Series (6 pages)
- 4200FA XT (1 page)
- RMTI-EMD-HT (2 pages)
- W7 Series (6 pages)
- HX7 (6 pages)
- PDP002Z (18 pages)
- RELIABILITY IN MOTION 1700 (39 pages)
- 1700 Series (2 pages)
- G3 TOSVERT-130 (62 pages)
- B-852-TS12-QP (55 pages)
- 1000 (4 pages)
- E3 (7 pages)
- Adjustable Speed Drive H3 (122 pages)
- 55611-001 (2 pages)
- Black Gold Series (2 pages)
- Dura-Bull TX (6 pages)
- Current Relay RC803A-HP1 (19 pages)
- 1800 SERIES (2 pages)
- Isolated-Redundant UPS System (2 pages)
- Tosvert VF-AS1 (312 pages)
- RELIABILITY IN MOTION 1000 (54 pages)
- REMOTE-D (2 pages)
- 15-80KVA (2 pages)